3 608 870 A47
Tightening Technology |
Bosch Rexroth AG 271
Nexo cordless Wi-Fi nutrunner
| 3 608 870 A47/2019-10
907
0
VW-XML: internal error
VW-XML protocol was terminated (config-
uration switched to inactive).
Check VW-XML configuration
Check and correct PLC assignment table
Reboot nutrunner
908
0
VW-XML: End with double
OS signal
VW-XML protocol was terminated (config-
uration switched to inactive).
Check VW-XML configuration
Check and correct PLC assignment table
Reboot nutrunner
909
0
VW-XML: End with OS signal
VW-XML protocol was terminated (config-
uration switched to inactive).
Check VW-XML configuration
Check and correct PLC assignment table
Reboot nutrunner
910
3
VW-XML: Serialization error
Port A
Incomplete or invalid response data.
Reboot nutrunner
911
3
VW-XML: Error port A parser
Master PC has sent an invalid VW-XML
stream to the nutrunner control.
Inform the manufacturer/operator of the
master PC
912
3
VW-XML: Serialization error
Port B
Incomplete or invalid dispatch data.
Reboot nutrunner
913
3
VW-XML: Error port B parser
Master PC has sent an invalid VW-XML
stream to the nutrunner control.
Inform the manufacturer/operator of the
master PC
914
0
VW-XML: Timeout
Port A for the answer from
Master PC
Master PC has not responded to port A
within the expected time (acknowledge
timeout).
Inform the manufacturer/operator of the
master PC
915
0
VW-XML: Reception error on
Port A
The connection on port A was terminated
by the master PC.
Inform the manufacturer/operator of the
master PC
Adjust VW-XML configuration
916
0
VW-XML: Timeout KeepAlive port
A
Master PC has not sent a telegram to port
A within the expected time (acknowledge
timeout).
Inform the manufacturer/operator of the
master PC
Adjust VW-XML configuration
917
0
VW-XML: Timeout
Port B for the answer from
Master PC
Master PC has not responded to port B
within the expected time (acknowledge
timeout).
Inform the manufacturer/operator of the
master PC
Adjust VW-XML configuration
918
0
VW-XML: Connection error on port
B
The connection on port B was terminated
by the master PC.
Inform the manufacturer/operator of the
master PC
919
0
VW-XML: Timeout KeepAlive port
B
Nexo has not sent a telegram to port B
within the expected time (Keepalive time-
out).
Reboot nutrunner
Update firmware, if necessary
920
0
VW-XML: No host name available Incorrect WLAN configuration.
Enter the host name in the WLAN configura-
tion.
921
0
VW-XML: Connection to port B
failed, no network resources avail-
able
No WLAN connection could be estab-
lished.
Check WLAN configuration
Reboot nutrunner
922
0
VW-XML: Connection to the mas-
ter PC on port B failed
No connection to the master PC on port B.
Inform the manufacturer/operator of the
master PC
Check firewall setting on master PC
923
4
VW-XML: Internal transmission er-
ror on port B
Queue overflow for transmission data.
Reboot nutrunner
924
0
VW-XML: Error PLC assignment ta-
ble
The PLC signals are incorrectly applied to
the PLC module
vwXml
or the PLC mod-
ule
vwXml
is not activated.
Activate PLC module
vwXml
in PLC table
and apply signals accordingly
Check and correct PLC assignment table
925
0
VW-XML database deleted
The VW-XML database has been deleted.
1000
4
BMW-TPC: Invalid configuration
settings
Faulty BMW-TPC configuration.
Correct the BMW-TPC configuration
1001
4
BMW-TPC: PLC module not con-
figured for execution
The PLC signals have been incorrectly ap-
plied to the
BmwTpc
PLC module. When
the data service was activated, the pro-
posed presettings were not adopted.
Check and correct the PLC assignment ta-
ble, that is, apply all program bits to the
PLC module
BmwTpc
Table 11–3: Error description
Error
code
Error
class
Description
Possible cause/consequence
Suggested solution