–
The system is in STAY mode and a zone intruder alarm (intruder alarm = instant / interior
instant / delay / interior delay / delay exit / interior delay exit / follower / interior
follower / 24h (can be silenced) / fire (can be silenced) / technical alarm (can be
silenced)) occurs.
–
The system is in AWAY mode and a tamper alarm occurs.
–
The system is disarmed and a zone tamper alarm occurs.
When the system is armed the output mode is a one pulse activation (1sec) (enabled / disable
option can be combined with disarm).
When the system is disarmed the output mode is a two pulse activation (1sec) (enabled /
disable option can be combined with arm).
When programming mode is entered the output mode is a one pulse activation (1sec)
(enabled / disable option).
08 - Internal Siren with Tamper
The output is operated when an internal siren with tamper occurs.
09 - Entry/Exit Delay Warning
Entry Delay Warning
This output is operated during the entry time.
The output is reset in the following cases:
–
The system is disarmed.
–
The entry time expires.
–
The programmed output time ends.
Exit Delay Warning
This output is operated during the exit time when the system is armed.
The output is reset in the following cases:
–
The system is disarmed.
–
The exit time expires.
–
The programmed output time ends.
If the output time is set to 000, the output will continue until the delay warning time ends.
10 - Telephone Line Fault
This output is operated when a telephone line fault occurs.
The output is reset in the following cases:
–
The telephone line is restored and the fault is reset.
–
The programmed output time ends.
If the output time is set to 000, the output will continue until the telephone line is restored
and the fault is reset.
11 - AC Power Supply Fault
This output is operated when an AC power fault occurs.
The output is reset in the following cases:
–
The AC power supply is restored and the fault is reset.
–
The programmed output time ends.
If the output time is set to 000, the output will continue until the AC power supply is restored
and the fault is reset.
12 – Battery fault
This output is operated when a low battery fault occurs.
AMAX panel
Settings | en
79
Bosch Sicherheitssysteme GmbH
Installation Manual
2015.05 | 06 | F.01U.309.277