The detectors (sensors) will be connected between zone and COM terminal through EOL
series connection (open triggered) or EOL parallel connection (short triggered).
COM
Zone
The panel sets the short / open as activate when connecting with single EOL.
The valid zone number is 1-8 forAMAX 2100 / 3000 / 3000 BE, 1-16 for AMAX 4000.
Dual EOL: If the tamper supervision is set, we only can use the NC contact point. The EOL
status is:
Loop resistance (ohm)
Zone Status
Min
Type
Max
o
1430
tamper
1650
2200
2750
normal
2970
4400
4950
triggered
5220
∞
tamper
Using one 2.2 kilo resistor as EOL of the tamper zone, which works together with the zone
EOL 2.2 kilo.
COM
Z3
BBBBB7DPSHU6ZLWFK
BBBBB=RQH6ZLWFK
1
2
NC (normally close): If the zone option is set to “NC”, an alarm occurs when the zone is
opened. When the zone is closed, the system is in normal mode.
NO (normally open): If the zone option is set to “NO”, an alarm occurs when the zone is
closed. When the zone is opened, the system is in normal mode.
On-board Tamper Input
A separate input is provided for enclosure tamper. The response time of the tamper input can
be programmed individually. The response time value range is 000.0-999.9 seconds.
Zone Name
This option is used to name zones. Therefore, the numbers on the text keypad function as an
alphabetical input.
Number on the
text keypad
Alphabetical input when number is pressed consecutively
1
. , ' ? ! " 1 - ( ) @ / : _ ¹ ² ³ © ® º « » µ ¶
2
a b c 2 æ å ä à á â ã ç ć č
3
d e f 3 è é ê ë ð ę
AMAX panel
Settings | en
63