![Bosch AMAX 4000 Installation Manual Download Page 149](http://html.mh-extra.com/html/bosch/amax-4000/amax-4000_installation-manual_39247149.webp)
Restore:
4
Remove the disturbing signal around the receiver, enable the wireless module and reset
the fault. For more information, refer to RF Devices, page 83.
Supervise:
1.
Report the receiver jam fault to configured destination when the fault is detected.
Slow flash FAULT indicator (refer to Keypad Indicators, page 8 for a detailed description).
2.
When the fault is reset, send the restored report to the configured destinations.
P
The FAULT indicator is turned off when there is no other system fault.
–
RF Sensor Failure
RF Sensor Missing
Condition:
A wireless zone sends no status report to the receiver in the RF supervision interval if a
wireless module is enabled.
Restore:
4
Make sure that all wireless zones are sending status reports to the receiver in the RF
supervision interval and reset the fault. For more information, refer to RF Devices, page
83.
Supervise:
1.
Report the wireless zone missing fault to configured destination when the fault is
detected.
Slow flash FAULT indicator (refer to Keypad Indicators, page 8 for a detailed description).
2.
When the fault is reset, send the restored report to the configured destinations.
P
The FAULT indicator is turned off when there is no other system fault.
RF Sensor Fault
Condition:
A wireless zone is in an abnormal condition (e.g. Remove the pyro from the smoke
detector/...) and a wireless module is enabled.
Restore:
4
Restore all wireless zones to a normal condition and reset the fault. For more
information, refer to RF Devices, page 83.
Supervise:
1.
Report the wireless zone fault to configured destination when the fault is detected.
Slow flash FAULT indicator (refer to Keypad Indicators, page 8 for a detailed description).
2.
When the fault is reset, send the restored report to the configured destinations.
P
The FAULT indicator is turned off when there is no other system fault.
–
RF Repeater Failure
1-8 RF Repeater 1-8 Missing
Condition:
No status report is send to the receiver in the RF supervision interval if a wireless module is
enabled.
Restore:
4
Make sure that status reports are sent to the receiver in the RF supervision interval and
reset the fault. For more information, refer to RF Devices, page 83.
Supervise:
1.
Report the repeater missing fault to configured destination when the fault is detected.
Slow flash FAULT indicator (refer to Keypad Indicators, page 8 for a detailed description).
2.
When the fault is reset, send the restored report to the configured destinations.
AMAX panel
Troubleshooting | en 149
Bosch Sicherheitssysteme GmbH
Installation Manual