Schedule Programming
This function is used to schedule operations according to the needs of the users. The
following operations can be scheduled:
–
Arming/disarming
–
Switching output on/off
–
Activating/deactivating users
It is possible to schedule up to 16 operations on a daily or hourly basis.
Notice!
Please note that this function can only be accessed and programmed via the PC software A-
Link Plus.
How to program a schedule
1.
Select the function you want to schedule. The following function can be selected:
Arm (area 1 – 16)
Disarm (area 1 – 16)
Switch on output (output 1 – 20)
Switch off output (output 1 – 20)
Activate user (user 1 – 250)
Deactivate user (user 1 – 250)
2.
Enter the desired time (hh:mm) and the date (dd/mm) for the schedule.
3.
Choose the selected days for the schedule (yes/no for each weekday).
4.
Optionally select a exception (e.g. for holidays)
P
The schedule is programmed and can be enabled/disabled by the user.
System View
Fault Analysis
This option display faults and tampers. The AMAX panel can display eight categories of 41
types of system faults and tampers.
How to display faults and tampers via a text keypad
In a text keypad the faults and tampers are displayed directly.
How to display faults and tampers via a master keypad
In a master keypad the system faults and tampers are displayed directly. After an area is
selected, the area-specific faults and tampers are displayed.
How to display faults and tampers via a LED/LCD keypad
To display faults and tampers via a LED/LCD keypad, perform the following steps:
1.
Enter your code + [2] [1] and press [#].
The system beeps twice. The FAULT indicator is extinguished and the STAY and AWAY
indicators flash. One of the number indicators is lit. Example: 2.
2.
Enter the number that is lit in the system. Example: 2.
One of the number indicators is lit. Example: 1.
3.
Repeat step 2 until there is no number lit anymore.
4.
Refer to the table Types of fault or tamper conditions for a description of the fault or
temper. The consecutively lit number indicators correspond to fault or tamper types.
Example: 2 – 1, which indicates a panel AC failure.
5.
If necessary press [0] to return to step 2.
6.
Press [#] to exit.
P
The STAY and AWAY indicators are extinguished and the FAULT indicator is lit.
6.5.2
74
en | Settings
AMAX panel
2015.05 | 06 | F.01U.309.277
Installation Manual
Bosch Sicherheitssysteme GmbH