Unverified Alarm Report
Enables / disables the option unverified alarm report. When a cross zone is triggered, but no
alarm is created, system creates an unverified alarm in order to report. System reports
unverified alarms if option unverified alarm report is enabled.
Zone Indication Keypad and Event Log
Zones may be indicated on LED/LCD keypads and in event logs with a number that are
different from the zone number used for programming and hardware input.
One area system
Zones are indicated on LED/LCD keypads according to the zone numbers. When one zone is
disabled the indication number of all following (higher) zone numbers will shift to a value
decreased by one.
Multi area system
Only zones assigned to one area are indicated on an area LED/LCD keypad in order beginning
with 1 and by following the order of zone numbers.
Examples:
AMAX 3000 / 3000 BE / 4000:
In a one area or area 1 system keypad the zone number 17 is indicated on a 16 zone LED/LCD
keypad. After disabling zone 16 (or another one in range 1 to 16), zone number 17 is indicated
on the LED/LCD keypad as zone number 16.
AMAX 2100:
In a one area system keypad the zone number 17 is indicated on an 8 zone LED/LCD keypad.
After disabling zone 5, zone number 17 is indicated on the LED/LCD keypad as zone number
5.
The following table shows the area assignment and keypad indication of zones in a multi area
system:
Zone Number
Area
Indication keypad area 1
Indication keypad area 1
1
2
1
2
2
2
3
1
1
4
1
2
5
1
3
6
1
4
7
2
3
8
2
4
9
2
5
10
2
6
11
1
5
12
1
6
6.3.5