Zone normal - no alarm / no report
–
Zone triggered – silent alarm / report
–
Zone triggered - during exit time – silent alarm / report
–
Zone triggered - during entry time – silent alarm / report
3.
STAY Arm: same as AWAY arm performance
–
A 24-hour panic zone has no restore report until the zone is restored.
19 – 24 Hour Fire
The 24-hour fire zone type performs as described below:
1.
Disarm:
–
Zone normal - no alarm / no report
–
Zone triggered - alarm / report
2.
AWAY Arm:
–
Zone normal - no alarm / no report
–
Zone triggered - alarm / report
–
Zone triggered - during exit time - alarm / report
–
Zone triggered - during entry time - alarm / report
3.
STAY Arm: same as AWAY arm performance
–
A fire zone does not send a restore report until the zone is restored.
20 – 24-Hour Fire with Verification
(Only possible for AMAX 4000 zone 1)
The 24-hour fire with verification zone type performs as described below:
1.
Disarm:
–
Zone normal - no alarm / no report
–
Zone triggered: After the first alarm, the AMAX panel performs a fire verification reset
(10 seconds) and then waits a period up to two minutes for a second alarm. If a
second alarm occurs within this period, the AMAX panel indicates a fire alarm.
Otherwise, the AMAX panel resets back to its normal condition. At the end of the two
minute period an unverified fire alarm is logged and reported. A fire zone does not
send a restore report until the zone is restored.
2.
AWAY Arm: same as disarm performance
3.
STAY Arm: same as disarm performance
21 – Tamper
The tamper zone type performs as described below:
1.
Disarm:
–
Zone normal - no alarm / no report
–
Zone triggered - alarm / report
2.
AWAY Arm:
–
Zone normal - no alarm / no report
–
Zone triggered - alarm / report
–
Zone triggered - during exit time - alarm / report
–
Zone triggered - during entry time - alarm / report
3.
STAY Arm: same as AWAY arm performance
–
A tamper zone does not send a restore report until the zone is restored.
22 – Bolt Contact
The bolt-contact zone type performs as described below:
60
en | Settings
AMAX panel
2015.05 | 06 | F.01U.309.277
Installation Manual
Bosch Sicherheitssysteme GmbH