Description
P036
P106
2
Start Source set to 2-Wire Control
P038
P108
2
Speed Reference set to 0–10 VDC
A051
t 201
6
Digital Input 1 set to Comm Port Force
Fan Remote Operator Station (Optional) (cont.)
Remote operator station wiring: Lenze SMVector VFDs (Powerfoil
®
8, Basic 6
®
, Pivot
™
, & Pivot
™
180 fans)
WARNING: The fan controllers contain high voltage capacitors that take time to discharge after removal of mains supply.
Before working on the fan controller, ensure isolation of mains supply from line inputs at the fan controller’s disconnect if
installed. Wait three (3) minutes for capacitors to discharge to safe voltage levels. Failure to do so may result in personal
injury or death. Darkened display LEDs are not an indication of safe voltage levels.
The following additional parameter changes are required for proper operation:
Jumper wire installation (shown above in yellow)
Big Ass
Solutions recommends making the parameter changes listed above prior to remote wiring or jumper wire installation. Jumpers
should be installed between terminals 1 and 17, terminals 13B and 13C, and terminals 4 and 16.
If an ESFR pilot relay is already installed on terminals 4 and 13A
, remove the N.O. relay common lead from terminal 4 and relocate
to terminal 16. This will prevent three wires from being landed under a single terminal. In this control arrangement, terminals 4 and 16
are both +15 VDC for digital reference.
10k
Ω
M
AN
U
AL
AU
TO
U
/
T1
V
/
T2
W
/
T3
PE
L1
L2
N
1 2 5 6
13A 13B 13C 14 30 16 17
25 4 11
1 2 5 6
13A
13B 13C
14 30
16 17
25
4
11
MANUAL
AUTO
OFF
NO
.3
.4
NO
.3
.4
BR
O
W
N
BL
A
CK
W
H
IT
E
RE
D
G
RE
EN
BL
U
E
YE
LL
O
W
YE
LL
O
W
YE
LL
O
W
BLA
CK
RED
WHITE
GREEN
BR
OWN
BL
UE
6 conductors, 20 AWG minimum
≤100 ft (30.5 m)
Parameter
Change to
P100: Start Control Source
1
P101: Standard Ref Source
1
P123: TB13C Function
7
P140: Relay Output Mode
16
Speed Control
Knob
Mode Selection
Knob
Both jumpers (1 to 4, 1 to 13B) must be removed if present!