BAFWORKS
®
INSTALLATION GUIDE
47
WWW.BIGASSSOLUTIONS.COM ©2013 DELTA T CORP. ALL RIGHTS RESERVED
BAFWORKS
®
INSTALLATION GUIDE
Setting Up the BAFWorks
®
Application (cont.)
Setting up fan group automation
The fan group automation feature lets users automatically maintain optimal fan speed and temperature based on whether it is the
cooling season or the heating season. Automation uses the temperature sensors connected to BAFWorks
®
to monitor the temperature
at the floor and ceiling levels. Based on the temperature readings, the fan group speed is automatically adjusted to maintain the
specified temperature settings.
To set up fan group automation:
1. If necessary, open BAFWorks.
2.
On the BAFWorks home screen, touch
Fans
.
3. Locate the fan group you want to work with, and then touch the
Detail Page
button for the group. The group details page appears.
Note: The application starts with a default group called “Fans.” See page 49 for instructions on adding and deleting groups.
4. Under
Automation
, select an automation mode:
• Manual
. Lets users manually change the speed of the fans to suit their temperature needs. The fans will not adjust speed
automatically.
• Summer
. During the cooling season, monitors the temperature at the floor level and adjusts the fan speed according to the
specified temperature and speed settings.
• Winter
. During the heating season, monitors the difference in temperatures at the floor and ceiling levels and automatically
adjusts the fan speed to maintain a uniform temperature between the floor and ceiling while using the lowest fan speed possible.
• Auto
. Combines the features of Summer and Winter modes and monitors the difference between the floor temperature and the
Winter maximum temperature setting. If the floor temperature is less than the Winter maximum temperature, Winter Mode is
used. If the floor temperature is greater than the Winter maximum temperature, Summer Mode is used.
5.
Next to Automation Changes, touch
Edit
. The Fans Automation page appears (Figure 5).
6.
Configure the settings, and then touch
Done
. See Figure 5 below for settings details.
7. Use the scheduling feature to specify when you want each automation mode to start. See page 63 for information on scheduling.
8.
When you are finished, touch
Done
on the group details page.
A. Automation Mode.
Select the automation mode. See step 4 above for details.
B. Summer Mode.
Set the maximum temperature (the temperature in ºF at which the fan will reach full speed) and the maximum fan
speed for the cooling season.
C. Winter Mode.
Set the maximum temperature (the temperature in ºF at which the fan will reach full speed) and the maximum fan
speed for the heating season.
D. Set Sensors.
Select the input module and port number of the floor temperature sensor and the ceiling temperature sensor. Ensure
this information is recorded on page 58 of this manual and on page 28 of the BAFWorks User Guide.
E. Current Temp.
Indicates the current temperature at the ceiling and floor levels as reported by the temperature sensors.
F. Admin Lock.
Lock or unlock access to the automation settings. This setting requires administrator password entry.
Note: The default
admin lock password is 1271. See page 55 for instructions on changing the password.
Figure 5–Fans Automation page
A
B
C
D
E
F
Summary of Contents for BAFWorks 3.0
Page 2: ...Customer Service 1 877 BIG FANS International 1 859 233 1271...
Page 62: ......
Page 80: ......
Page 83: ......
Page 84: ...003915 01 2425 Merchant St Lexington KY 40511 1 877 BIG FANS WWW BIGASSFANS COM REV I...