BAFWORKS
®
INSTALLATION GUIDE
WWW.BIGASSSOLUTIONS.COM ©2013 DELTA T CORP. ALL RIGHTS RESERVED
38
Fan Remote Operator Station (Optional) (cont.)
Remote operator station wiring: 200V–240V & 400V–480V Delta E series VFDs (Powerfoil
®
X Series fans)
WARNING: The fan controllers contain high voltage capacitors that take time to discharge after removal of mains supply.
Before working on the fan controller, ensure isolation of mains supply from line inputs at the fan controller’s disconnect if
installed. Wait three (3) minutes for capacitors to discharge to safe voltage levels. Failure to do so may result in personal
injury or death. Darkened display LEDs are not an indication of safe voltage levels.
The following additional parameter changes are required for proper operation:
Jumper wire installation (shown above in yellow)
Big Ass
Solutions recommends making the parameter changes listed above prior to remote wiring or jumper wire installation. A new
jumper should be installed between terminals MI5 and MI6.
Parameter
Change to
02-00: First Master Frequency Command
"1" 0 to +10 V from AVI Terminal
02-01: First Operation Command
"1" External Terminals
04-07: Multifunction Input Terminal 5
"20" Communication Command Enable
10k
Ω
M
AN
U
AL
AU
TO
NO
.3
.4
NO
.3
.4
RA RB RC
AVI
NPN
MANUAL
AUTO
OFF
M
I1
M
I5
M
I6
DC
M
AC
M
AV
I
10
V
BR
OW
N
BL
U
E
YE
LL
O
W
G
RE
EN
BL
AC
K
W
H
IT
E
RE
D
BLA
CK
RED
WHITE
GREEN
BR
OWN
BL
UE
6 conductors, 20 AWG minimum
≤100 ft (30.5 m)
Speed Control
Knob
Mode Selection
Knob
All three blue jumpers (RA to MI1, RB to MI6, RC to DCM) must be removed if present!