TRANSFER SETTINGS
Setpoint
Ranges
Increment
Accuracy
†
Manual Transfer (cont.)
Hot Parallel Transfer
Delta Phase Angle Limit*
0.0 to 90.0 Degrees
0.1 Degree
0.5 Degree
Delta Voltage Limit
0 to 60 V
1 V
0.5 V or
2%
Delta Frequency Limit
0.02 to 0.50 Hz
0.01 Hz
0.01 Hz or
5%
Time Window
1.0 to 50.0 Cycles
0.5 Cycle
1 Cycle
Tripping Command
Time Delay**
0.0 to 30.0 Cycles
0.5 Cycle
1 Cycle
* Accuracy defined at a constant frequency with a delta frequency of zero (0).
** This time delay is only used in the Manual Transfer to implement a Hot Parallel Transfer (make-before-
break).
Auto Trip
Trip Originally Closed
Enable/Disable
____
____
Breaker
Trip Breaker
Enable/Disable
____
____
Just Closed
Tripping Command
Time Delay
0.0 to 50.0 Cycles
0.5 Cycle
1 Cycle