System Setup and Setpoints – 4
4–51
AUTOMATIC TRANSFER SETTINGS/DELAYED
IN-PHASE TRANSFER TAB
Path:
System/Setup/Setpoints/Automatic Transfer
Settings/Delayed In-Phase Transfer
Figure 4-51, illustrates the MBTS Automatic Transfer
Settings found under the Delayed In-Phase Transfer
Tab on the Automatic Transfer Settings dialog
screen.
The top right corner of the display includes
a command button that will disable or enable the
automatic Delayed In-Phase Transfer. This selection
allows the automatic Delayed In-Phase Transfer to
be disabled (or enabled) independent from the
Automatic Fast, Residual and Fixed Time Transfers.
Typically this feature is used to disable the other
types of transfers if needed.
Appendix F
, Time
Sequence of Transfer Logic includes the timing
diagrams of the Simultaneous and Sequential
Transfers. All transfers are enabled at the same
time and the characteristics of the motor bus voltage
decay determines which type of transfer is possible.
This feature allows the user to disable the individual
types of transfers if desired.
Automatic Delayed In-Phase Transfer/Delta
Voltage Limit
The Delta Voltage Limit
can be set from 0 to120 volts.
The Delta Voltage is the voltage difference between
the motor bus and the new source. This setting can be
disabled. If it is disabled then this parameter is not
used as a condition to execute a Delayed In-Phase
Transfer.
Automatic Delayed In-Phase Transfer/Delta
Frequency Limit
The Delta Frequency Limit
can be set from 0.10 to
10.00 Hz. The Delta Frequency is the frequency
difference between the motor bus and the new source.
This setting cannot be disabled. The frequency is
always one of the parameters used to determine if a
Delayed In-Phase Transfer can be executed.
Automatic Delayed In-Phase Transfer/Time
Window
The Time Window can be set from 10 to 600 cycles.
The Time Window defines the window of opportunity
for a Delayed In-Phase Transfer. The time window
starts when the transfer is initiated and ends at the
selected time limit. If a Delayed In-Phase Transfer
has not been completed by the end of this time
window then the Delayed In-Phase Transfer is
disabled and will no longer be attempted. A Residual
or Fixed Time Transfer is still possible.
Figure 4-51 Automatic Transfer Settings Delayed In-Phase Transfer Tab Dialog Screen
Summary of Contents for M-4272
Page 1: ...Instruction Book Book 1 of 2 M 4272 Motor Bus Transfer System ...
Page 45: ...xviii M 4272 Instruction Book This Page Left Intentionally Blank ...
Page 200: ...System Setup and Setpoints 4 4 89 Figure 4 93 ISSLogic Function Dialog Screen ...
Page 207: ...M 4272 Instruction Book 4 96 This Page Left Intentionally Blank ...
Page 214: ...Declaration of Conformity Appendix I I 1 IAppendix I Declaration of Conformity ...
Page 215: ...M 4272 Instruction Book I 2 This Page Left Intentionally Blank ...