System Setup and Setpoints – 4
4–7
6.
Press the Right arrow pushbutton until
the following is displayed:
USER CONTROL NUMBER
vers sn access NUMBER
7.
Press
ENTER
, the following will be
displayed:
USER CONTROL NUMBER
1
8.
Input the desired User Control Number
as follows:
a.
Utilizing the Up and Down arrow
pushbuttons select the desired first
digit.
b.
Press the Left arrow pushbutton once,
then repeat the previous step as
necessary to input the desired User
Control Number.
c.
When the desired User Control Number
has been input, then press
ENTER
.
The following will be displayed:
USER CONTROL NUMBER
vers sn access NUMBER
9.
Press
Exit.
HMI System OK LED Setup
1.
Press the
ENTER
pushbutton.
2.
If Level Access is active, the following
is displayed:
ENTER ACCESS CODE
0
a.
Input the required Access Code, then
press
ENTER
.
b.
If the proper Access Code has been
entered, the HMI will return:
LEVEL #(1,2 or 3)
Access Granted!
INIT TRANSFER
INIT
rmte_lcal
c.
Go to step 4.
3.
If Level Access is not active, then the
following is displayed:
INIT TRANSFER
INIT
rmte_lcal
▲
▲
▲
▲
▲
CAUTION:
Do not enter DIAGNOSTIC MODE
when protected equipment is in service. Entering
DIAGNOSTIC MODE when protected equipment is
in service removes all protective functions of the
MBTS.
4.
Press the right arrow pushbutton until
the following is displayed:
SETUP UNIT
stat comm SETUP
5.
Press
ENTER,
the following will be
displayed:
SOFTWARE VERSION
VERS sn access number
6.
Press the right arrow pushbutton until
the following is displayed:
DIAGNOSTIC MODE
time error eth DIAG
7.
Press
ENTER
, the following warning will
be displayed:
PROCESSOR WILL RESET!
ENTER KEY TO CONTINUE
▲
▲
▲
▲
▲
CAUTION:
Do not enter DIAGNOSTIC MODE
when protected equipment is in service. Entering
DIAGNOSTIC MODE when protected equipment is
in service removes all protective functions of the
MBTS.
8.
Press
ENTER
, the relay will reset and
DIAGNOSTIC MODE
will be temporarily
displayed followed by:
OUTPUT TEST (RELAY)
OUTPUT input led module
9.
Press the Right arrow pushbutton until
the following is displayed:
FLASH SYS OK LED
com3 clock LED cal
Summary of Contents for M-4272
Page 1: ...Instruction Book Book 1 of 2 M 4272 Motor Bus Transfer System ...
Page 45: ...xviii M 4272 Instruction Book This Page Left Intentionally Blank ...
Page 200: ...System Setup and Setpoints 4 4 89 Figure 4 93 ISSLogic Function Dialog Screen ...
Page 207: ...M 4272 Instruction Book 4 96 This Page Left Intentionally Blank ...
Page 214: ...Declaration of Conformity Appendix I I 1 IAppendix I Declaration of Conformity ...
Page 215: ...M 4272 Instruction Book I 2 This Page Left Intentionally Blank ...