M-4272 Instruction Book
2–10
2.
Select either
Device ON
or
Device OFF
,
then select
Save
.
3.
Verify that the MBTS is in the desired
mode by observing the Device On/Off
Mode status indicator on the Secondary
Metering and Status screen (System
Status).
Device ON/OFF (MBTS Front Panel)
To switch the MBTS On or OFF from the Front
Panel perform the following:
1.
Press the
ENTER
pushbutton.
2.
If Level Access is active, the following is
displayed:
ENTER ACCESS CODE
0
a. Input the required Access Code, then
press
ENTER
.
b. If the proper Access Code has been
entered, the HMI will return:
LEVEL #(1,2 or 3)
Access Granted!
INIT TRANSFER
INIT
rmte_lcal
c. Go to Step 4.
3.
If Level Access is not active, then the
following is displayed:
INIT TRANSFER
INIT
rmte_lcal
4.
Press the Right arrow pushbutton until
the following is displayed:
DEVICE ON/OFF
ON_OFF exit
5.
Press
ENTER,
the following will be
displayed:
DEVICE MODE
ON off
6.
Press the Left or Right arrow pushbutton
as necessary to select the desired Device
Mode (upper case).
7.
Press
ENTER
. The following will be
displayed:
DEVICE ON/OFF
ON_OFF exit
8.
The MBTS is now in the selected Device
Mode. Press
EXIT
as necessary to return
to the Main Menu.
System Error Codes and Output Counters
The System Error Codes and Output Counters feature
provides the user with the ability to view and clear
system Error Codes, Processor Resets, Alarm
Counters, Power Loss Counter and Output Counters.
Also, Checksums can be viewed for Calibration and
Setpoints.
Reset/View System Error Codes and Output
Counters (ISScom
®
)
To view and/or Reset System Error Codes and
Output Counters utilizing ISScom
TM
perform the
following:
Q
NOTE
: Communication must be established with
the target MBTS for this procedure.
1.
From the ISScom Main Screen menu bar
select
Tools/System Error Codes/
Counters
. ISScom will display the
System Error Codes and Output Counters
dialog screen (Figure 2-8).
2.
Select the desired System Error Code,
Processor Reset, Alarm Counter, Power
Loss Counter to be reset, then select
OK
. ISScom will return to the Main Menu.
Clear Alarm Counters (MBTS Front Panel)
To reset Alarm Counters from the Front Panel perform
the following:
1.
Press the
ENTER
pushbutton.
2.
If Level Access is active, the following is
displayed:
ENTER ACCESS CODE
0
a. Input the required Access Code, then
press
ENTER
.
Summary of Contents for M-4272
Page 1: ...Instruction Book Book 1 of 2 M 4272 Motor Bus Transfer System ...
Page 45: ...xviii M 4272 Instruction Book This Page Left Intentionally Blank ...