3–13
ISScom – 3
Path
: System / Setup / Monitor / Secondary Metering and Status
Figure 3-17 Secondary Metering and Status Screen
▲
CAUTION:
Do not use the Delta Phase Angle OK,
Delta Voltage OK or Delta Frequency OK status
indicators of the ISScom
®
software to determine
when to manually initiate a transfer. There is
sufficient delay in the communications between the
MBTS and the ISScom such that these indications
do not provide “live” information. Always use the
status indicators of the MBTS front panel. These
indicators use the manual transfer settings to
determine when a parameter is OK. If manual transfer
is disabled a warning message “Manual Transfer
Blocked” will be displayed and no transfer will occur.
The Function Status window displays the status of
various functions, with “T” representing the function
which has timed out, and “P” representing the function
which has picked up and is timing.