M-4272 Digital Motor Bus Transfer System
†
Select the greater of these accuracy values. Accuracy applies to sinusoidal voltage with constant amplitude and
frequency. Values in parentheses apply to 1 A CT secondary rating.
50
BF1
50
BF2
27B
FUNCTIONS
Setpoint
Ranges
Increment
Accuracy
†
27B Bus Phase Undervoltage
Pickup #1, #2, #3, #4
5 to 120 V
1 V
0.5 V or
2%
Inhibit Setting**
5 to 120 V
1 V
0.5 V or
2%
Time Delay
1 to 8160 Cycles
1 Cycle
-1 to +3 Cycles or
0.5%*
* The pickup and time delay accuracies apply to 60 HZ models at a range of 57 to 63 Hz, and to 50 Hz models at
a range of 47 to 53 Hz. Beyond these ranges, the time delay accuracy is 6 Cycles or 0.75% for the bus frequency
down to 25 Hz. The time delay accuracy is
O
O
O
O
O
20 Cycles or 1% for the bus frequency at a range of 5 to 25 Hz.
** The Voltage Inhibit setting can be enabled or disabled.
27B #1 is the Bus Phase Undervoltage initiate function that is used for Automatic Transfer from S1 to S2 direction.
27B #2 is the Bus Phase Undervoltage initiate function that is used for Automatic Transfer from S2 to S1 direction.
27B #3 can be used for load shedding.
27B #4 can be used for alarm or trip function.
The 27B functions are applicable only when the bus phase voltage input is applied.
50S1 Instantaneous Phase Overload Detection (Source 1)
Pickup #1, #2
1.0 to 100.0 A
0.1 A
0.1 A or
3%
(0.2 to 20.0 A)*
(
0.02 A or
3%)
Time Delay
1 to 8160 Cycles
1 Cycle
2 Cycles or
1%
* Values in parentheses apply to 1A secondary rating. Since this is only a single phase element, the 50S1
Function can only be used for overload detection and not used for overcurrent protection.
50S2 Instantaneous Phase Overload Detection (Source 2)
Pickup #1, #2
1.0 to 100.0 A
0.1 A
0.1 A or
3%
(0.2 to 20.0 A)*
(
0.02 A or
3%)
Time Delay
1 to 8160 Cycles
1 Cycle
2 Cycles or
1%
* Values in parentheses apply to 1A secondary rating. Since this is only a single phase element, the 50S2
Function can only be used for overload detection and not used for overcurrent protection.
50BF-1 Breaker Failure (Source 1)
Pickup Current
0.10 to 10.00 A
0.01 A
0.1 A or
2%
(0.02 to 2.00 A)*
(
0.02 A or
2%)
Time Delay
1 to 30 Cycles
1 Cycle
1 Cycle
50BF-1 can be initiated from designated M-4272 output contacts or programmable inputs.
* Value in parentheses apply to 1A Secondary Rating
50BF-2 Breaker Failure (Source 2)
Pickup Current
0.10 to 10.00 A
0.01 A
0.1 A or
2%
(0.02 to 2.00 A)*
(
0.02 A or
2%)
Time Delay
1 to 30 Cycles
1 Cycle
1 Cycle
50BF-2 can be initiated from designated M-4272 output contacts or programmable inputs.
* Value in parentheses apply to 1A Secondary Rating
50
S1
50
S2
Summary of Contents for M-4272
Page 1: ...Instruction Book Book 1 of 2 M 4272 Motor Bus Transfer System ...
Page 45: ...xviii M 4272 Instruction Book This Page Left Intentionally Blank ...
Page 200: ...System Setup and Setpoints 4 4 89 Figure 4 93 ISSLogic Function Dialog Screen ...
Page 207: ...M 4272 Instruction Book 4 96 This Page Left Intentionally Blank ...
Page 214: ...Declaration of Conformity Appendix I I 1 IAppendix I Declaration of Conformity ...
Page 215: ...M 4272 Instruction Book I 2 This Page Left Intentionally Blank ...