M-4272 Instruction Book
2–2
ENTER Pushbutton
The
ENTER
pushbutton is used to choose a
highlighted menu selection, to replace a setting or
other programmable value with the currently displayed
value, or to move down within the menu tree.
System OK LED
The Green
SYSTEM OK
LED is controlled by the
unit's microprocessor. A flashing
SYSTEM OK
LED
indicates proper program cycling. The LED can also
be programmed to be continuously illuminated to
indicate proper program cycling.
Diagnostic/Time Sync LED
The Green
DIAG/TIME SYNC
LED will illuminate to
indicate that the IRIG-B time signal is received and
the internal clock is synchronized with the IRIG-B
time signal. IRIG-B time information is used to
accurately tag target and oscillograph events.
The LED will flash when a self-test error is detected.
The LED will flash the Error Code number; for
example, for Error Code 32, the LED will flash 3
times, followed by a short pause, and then flash 2
times, followed by a long pause, then repeat LED
flash sequence. The Error Code number is also
displayed on the M-3931 HMI screen.
Breaker Status LEDs
The Red
SOURCE 1
BRKR CLOSED
,
SOURCE 2
BRKR CLOSED
LEDs and the Green
SOURCE 1
BRKR OPEN
,
SOURCE 2
BRKR OPEN
LEDs will
illuminate when the selected breaker status input is
closed. Table 2-1 presents the available input
configurations for the Breaker Status LEDs.
SOURCE 1 BREAKER STATUS LEDs
S1 52a Closed
(Input 1)
S1 52b Open
(Input 2)
RED (CLOSED)
S1 52a and S1 52b
(Inputs 1 and 2)
GREEN (OPEN)
S1 52a Open
(Input 1)
S1 52b Closed
(Input 2)
S1 52a and S1 52b
(Inputs 1 and 2)
SOURCE 2 BREAKER STATUS LEDs
S2 52a Closed
(Input 4)
S2 52b Open
(Input 5)
S2 52a and S2 52b
(Inputs 4 and 5)
GREEN (OPEN)
S2 52a Open
(Input 4)
S2 52b Closed
(Input 5)
S2 52a and S2 52b
(Inputs 4 and 5)
RED (CLOSED)
Table 2-1 Breaker Status LED Input
Configurations
Power Supply #1 & #2 LED
The Green
PS
LED indicator will remain illuminated
for the appropriate power supply whenever power is
applied to the unit and the power supply is operating
correctly. The two power supplies are not redundant
and the unit requires both supplies to operate for
correct unit functioning.
M-3972 Status Module
The Status module includes 24 Status LEDs, and 8
Output Status LEDs. The 24 Status LEDs are
preassigned to provide the status of specific functions
and features. The Status LEDs provide the following
indication:
•
When a function is in a "Picked Up"
(exceeded the setpoint value) condition,
the assigned Status Indicator will illuminate
when the "Status Reset" pushbutton is
depressed and held.
•
When a function is in a "Picked Up"
(exceeded the setpoint value) condition,
and the Time Delay timer has timed out
the assigned Status Indicator will illuminate
as well as any assigned Output LEDs.
•
Transfer Conditions
When a condition exists that causes the operation of
Outputs 1 through 8, the assigned STATUS
LED on
the M-3872 Status Module will illuminate. Status
Module LEDs will remain illuminated until the condition
causing the trip is cleared, and the operator presses
the
"
STATUS RESET
"
pushbutton.
Output and Input Status LEDs
When a condition exists that causes the operation of
Outputs 9 through 16 or Inputs 7 through 18 the
assigned Status LED on the M-4272 Front Panel
will illuminate. The Status LEDs will remain
illuminated until the condition causing the operation
is cleared, and the operator presses the
"
STATUS
RESET
"
pushbutton.
Trip (TCM) and Close (CCM) Circuit Monitor
Status LEDs
The Trip and Close Circuit Monitor LEDs provide the
status of the Trip and Close circuits. If a Trip or
Close circuit is open (cannot perform either trip or
close function) the corresponding LED will be
illuminated until the open circuit is corrected.
Summary of Contents for M-4272
Page 1: ...Instruction Book Book 1 of 2 M 4272 Motor Bus Transfer System ...
Page 45: ...xviii M 4272 Instruction Book This Page Left Intentionally Blank ...
Page 200: ...System Setup and Setpoints 4 4 89 Figure 4 93 ISSLogic Function Dialog Screen ...
Page 207: ...M 4272 Instruction Book 4 96 This Page Left Intentionally Blank ...
Page 214: ...Declaration of Conformity Appendix I I 1 IAppendix I Declaration of Conformity ...
Page 215: ...M 4272 Instruction Book I 2 This Page Left Intentionally Blank ...