–20–
M-4272 Digital Motor Bus Transfer System
INITIA
TION
TRIP COMMAND
10ms DELA
Y
15
TO 30 CYCLES
BREAKER OPEN
ENABLE FAST
FAST
TRANSFER
TIME WINDOW*
BREAKER OPENING
TIME
1
TO 10 CYCLES
DELA
YED-IN-PHASE
TRANSFER
ENABLE
DELA
YED-IN-PHASE
TRANSFER
TIME
WINDOW*
10
TO 600 CYCLES
4ms DELA
Y
RESIDUAL
VOL
TAGE
TRANSFER*
RESIDUAL
VOL
TAGE
TRANSFER
ENABLE
FIXED-TIME
TRANSFER
ENABLE
* CLOSE OUTPUT
COMMAND
TERMINA
TES
ALL
TRANSFER
TIME WINDOWS.
3000
CYCLES
MAXIMUM
INCOMPLETE
TRANSFER
LOCKOUT
TIME
TRANSFER IN PROCESS
TERMINA
TES WITH CLOSE OUTPUT
COMMAND
FIXED-TIME
TRANSFER*
30
TO 1000 CYCLES
30 CYCLES DELA
Y
TRANSFER
Figure 3
Time Sequence of Transfer Logic in Sequential Transfer Mode
Summary of Contents for M-4272
Page 1: ...Instruction Book Book 1 of 2 M 4272 Motor Bus Transfer System ...
Page 45: ...xviii M 4272 Instruction Book This Page Left Intentionally Blank ...
Page 200: ...System Setup and Setpoints 4 4 89 Figure 4 93 ISSLogic Function Dialog Screen ...
Page 207: ...M 4272 Instruction Book 4 96 This Page Left Intentionally Blank ...
Page 214: ...Declaration of Conformity Appendix I I 1 IAppendix I Declaration of Conformity ...