System Setup and Setpoints – 4
4–11
ISScom COM Port Definitions and System’s
Communication Address
To setup the COM Ports and Communication
Addresses perform the following:
NOTE
: Communication must be established with
the target MBTS for this procedure.
1.
From the ISScom
®
Main Screen menu
select
Tools/System Comm Setup
.
ISScom will display the System
Communication Setup dialog screen
(Figure 4-7).
The System COM Port that is in use will
be indicated at the top of the display.
2.
Select the desired COM Port to be setup
(1, 2 or 3).
3.
Enter the desired “Dead Sync Time” (2
to 3000 msec).
This delay establishes the line idle time
to re-sync packet communication. Dead
sync time should be programmed based
on the channel’s baud rate.
Baud Rate
Dead-Sync Time
9600
4 ms
4800
8 ms
2400
16 ms
1200
32 ms
Table 4-1 Dead-Sync Time
4.
Enter the desired “Baud Rate” (1200 to
9600). COM2 and COM3 share the same
baud rate (see Section 5.4,
Circuit
Board Switches and Jumpers
).
5.
Enter the desired “Stop Bits” value (1 or
2).
6.
Enter the desired “Parity” (None, odd or
even).
Figure 4-7 System Communication Setup Dialog Screen
Summary of Contents for M-4272
Page 1: ...Instruction Book Book 1 of 2 M 4272 Motor Bus Transfer System ...
Page 45: ...xviii M 4272 Instruction Book This Page Left Intentionally Blank ...
Page 200: ...System Setup and Setpoints 4 4 89 Figure 4 93 ISSLogic Function Dialog Screen ...
Page 207: ...M 4272 Instruction Book 4 96 This Page Left Intentionally Blank ...
Page 214: ...Declaration of Conformity Appendix I I 1 IAppendix I Declaration of Conformity ...
Page 215: ...M 4272 Instruction Book I 2 This Page Left Intentionally Blank ...