System Setup and Setpoints – 4
4–69
50 SOURCE 1 INSTANTANEOUS
PHASE OVERLOAD DETECTION
Path:
System/Setup/Setpoints/50S1
The Instantaneous Phase Overload (50S1) Function
provides fast tripping for high Source 1 currents.
The settings must be set such that they will not
Figure 4-69 Source 1 Instantaneous Phase Overload Detection Dialog Screen
Figure 4-70 Source 1 Instantaneous Phase Overload Detection I/O Selection Dialog Screen
pickup for normal load current conditions. Ranges
and Increments are presented in Figure 4-70. Since
this is only a single phase element, the 50S1
Function can only be used for overload detection
and not used for overcurrent protection. The current
(I
R
) is equal to the primary current (I
p
) divided by the
appropriate CT ratio.