![BECKWITH ELECTRIC M-4272 Instruction Book Download Page 165](http://html.mh-extra.com/html/beckwith-electric/m-4272/m-4272_instruction-book_2719813165.webp)
M-4272 Instruction Book
4–54
Automatic Fixed Time Transfer/Time Delay
The Time Delay
setting can be set from 30 to 1000
cycles. When the conditions are met for a Fixed Time
Transfer the Time Delay starts timing. When the Time
Delay times out, a close command is sent to the Load
Shedding Time Delay. When the Load Shedding Time
Delay times out the close command is sent to the new
source breaker. No other parameters are monitored.
If Fixed Time Transfer has been selected as a Load
Shedding Function Selection in the Common
Settings (Figure 4-46), then the signal sent to the
Load Shedding Output will be true when the Fixed
Time Transfer, Time Delay times out.
These settings cannot be disabled, they are the only
parameters used as the condition to execute a Fixed
Time Transfer. There is no Time Window for the Fixed
Time Transfer. However, it must be completed by the
Incomplete Transfer Lockout Time Limit setting.
Automatic Fixed Time Transfer/Load Shedding
Time Delay
The Load Shedding Time Delay
can be set from 2 to
100 cycles. The Load Shedding Time Delay defines
the time period from when the Fixed Time Transfer,
Time Delay times out and when the close command
is sent to the new source breaker.
Automatic Fixed Time Transfer/Blocking Inputs
Selection
The Blocking Inputs Selection
button opens the Blocking
Inputs Selection dialog screen (Figure 4-50). Any Input
or the Fuse Loss (FL) function can be selected to block
a Fixed Time Transfer. When an input is selected, it is
not grayed out in other types of transfers.
Automatic Fixed Time Transfer Save/Cancel
The Save selection saves the Automatic Fixed
Time Transfer Tab settings either to an open file or
to the target MBTS. Cancel, returns the user to the
previous open screen.
The conditions that are necessary to execute a
delayed Fixed Time Transfer are:
•
No Lockout/Blocking conditions exist.
•
The conditions for a Fast Transfer have
not been matched.
•
The conditions for an In-Phase transfer
have not been matched.
•
The motor bus voltage drops below the
Residual Voltage Transfer limit setting
(adjustable from 0 to 60 V) within the
incomplete transfer lockout time limit
setting (50 to 3000 cycles).
Figure 4-53 Automatic Transfer Settings Fixed Time Transfer Tab Dialog Screen
Summary of Contents for M-4272
Page 1: ...Instruction Book Book 1 of 2 M 4272 Motor Bus Transfer System ...
Page 45: ...xviii M 4272 Instruction Book This Page Left Intentionally Blank ...
Page 200: ...System Setup and Setpoints 4 4 89 Figure 4 93 ISSLogic Function Dialog Screen ...
Page 207: ...M 4272 Instruction Book 4 96 This Page Left Intentionally Blank ...
Page 214: ...Declaration of Conformity Appendix I I 1 IAppendix I Declaration of Conformity ...
Page 215: ...M 4272 Instruction Book I 2 This Page Left Intentionally Blank ...