M-4272 Instruction Book
4–48
The selected input will initiate an Automatic Transfer
from Source 2 to Source 1. If the Source 1 breaker
is closed and the Source 2 breaker is open the
transfer is blocked since the breakers are in the
wrong positions for this transfer and the transfer is
ignored. Since Automatic Transfers can occur in
either direction, a separate Transfer Initiate Input is
needed.
When an input has been selected it will be grayed
out in other dialog screens that provide input
selection since it has already been assigned.
Automatic Transfer/27-S1 Initiate (S1 to S2)
The 27-S1 Initiate (S1 to S2) opens a dialog screen
similar to Figure 4-48 that allows the user to select
an input or inputs that are used to initiate Automatic
Transfers from an external 27 device.
The selected input will initiate an Automatic Transfer
from Source 1 to Source 2. If the Source 2 breaker
is closed and the Source 1 breaker is open the
transfer is blocked since the breakers are in the
wrong positions for this transfer and the transfer is
ignored. Since Automatic Transfers can occur in
either direction a separate Transfer Initiate Input is
needed.
When an input has been selected it will be grayed
out in other dialog screens that provide input
selection since it has already been assigned.
Automatic Transfer/27-S2 Initiate (S2 to S1)
The 27-S2 Initiate (S2 to S1) opens a dialog screen
similar to Figure 4-48 that allows the user to select
an input or inputs that are used to initiate Automatic
Transfers from an external 27 device.
The selected input will initiate an Automatic Transfer
from Source 2 to Source 1. If the Source 1 breaker
is closed and the Source 2 breaker is open the
transfer is blocked since the breakers are in the
wrong positions for this transfer and the transfer is
ignored. Since Automatic Transfers can occur in
either direction a separate Transfer Initiate Input is
needed.
When an input has been selected it will be grayed
out in other dialog screens that provide input
selection since it has already been assigned.
Automatic Transfer Settings Setup Tab/Save/
Cancel
— The Save selection (Figure 4-47) saves
the Automatic Transfer settings either to an open
file or to the target MBTS. Cancel, returns the user
to the previous open screen.
Automatic Transfer/Auto Transfer Block
The Auto Transfer Block selection opens the Auto
Transfer Block dialog screen (Figure 4-48) that
allows the user to select an input that is used to
block Automatic Transfers. When an input has
been selected it will be grayed out in other dialog
screens that provide input selection since it has
already been assigned.
Figure 4-48 Automatic Transfer Block Input
Settings Dialog Screen
Automatic Transfer/86P-S1 Initiate (S1 to S2)
The 86P-S1 Initiate (S1 to S2) opens a dialog
screen similar to Figure 4-48 that allows the user to
select an input that is used to initiate Automatic
Transfers from an 86P Lockout MBTS.
The selected input will initiate an Automatic Transfer
from Source 1 to Source 2. If the Source 2 breaker
is closed and the Source 1 breaker is open the
transfer is blocked since the breakers are in the
wrong positions for this transfer, the transfer is
ignored. Since Automatic Transfers can occur in
either direction, a separate Transfer Initiate Input is
needed.
When an input has been selected it will be grayed
out in other dialog screens that provide input
selection since it has already been assigned.
Automatic Transfer/86P-S2 Initiate (S2 to S1)
The 86P-S2 Initiate (S2 to S1) opens a dialog
screen similar to Figure 4-48 that allows the user to
select an input or inputs that are used to initiate
Automatic Transfers from an 86P Lockout MBTS.
Summary of Contents for M-4272
Page 1: ...Instruction Book Book 1 of 2 M 4272 Motor Bus Transfer System ...
Page 45: ...xviii M 4272 Instruction Book This Page Left Intentionally Blank ...
Page 200: ...System Setup and Setpoints 4 4 89 Figure 4 93 ISSLogic Function Dialog Screen ...
Page 207: ...M 4272 Instruction Book 4 96 This Page Left Intentionally Blank ...
Page 214: ...Declaration of Conformity Appendix I I 1 IAppendix I Declaration of Conformity ...
Page 215: ...M 4272 Instruction Book I 2 This Page Left Intentionally Blank ...