5.6. Validation
To guarantee the functioning of the implemented safety function, the user must test the parameters
and the links. After commissioning and parametrisation have been completed, the user must test
these functions. This test must be documented. Documenting is supported by the validation
assi
stant (c. f. the chapter “Safety inspection“).
5.6.1. Generating a validation report
In SafePLC
2
, a validation report can be generated with
.
A *.pdf file is created.
To guarantee the functioning of the implemented safety function, the user must test the parameters
and the links. After commissioning and parametrisation have been completed, the user must test
these functions. This functional testing must be documented. Documenting is supported by the
parametrizing software SafePLC
2
.
On the last two pages, general details can be furnished with respect to the installation. The last
page of the validation report contains the itemization of the safety-relevant inspection.
It is mandatory to carry out the safety inspections contained in the validatíon report
By his signature, the responsible tester of the safety module confirms confirms that the CRC
displayed in the programming surface is has identity with the CRC defined in the SCU assembly.