Programming manual SCU-series
HB-37500-820-10-12F-EN SCU Programming manual
Page 113 of 252
Status: 19.03.2021
Step: individual check of the system components
This section contains control boxes that should be marked if the given information is correct.
Visual check for personal injuries and correct fastening:
Component documentation is available:
Visual check for deviations from the installation guideline:
Device type:
Enter device type, e. g. SMX 10, SMX 100 usw.
Serial number:
Serial number of safety module (label)
CRC device configuration:
Signature for the programme and for the parameter data
CRC parameters:
Signature for the parameter data
CRC programme
Signature for the programme
Extension device:
Description of extended devices
Transmission meter:
This field can also be edited.
Number of axles :
Total number of axles
Functional test:
To create the validation report, the correct programme data and the correct parameter data
must be loaded!
The test engineer must revalidate all configured data in the printed report by verifying the
programmed functions on the equipment/the device.
All set limit values of the monitoring function used must be checked for correctness. The reaction
times mentioned in the installation manual must be observed.
A successfully completed validation should be completed by clicking on the button
“
Lock
validation
“.
NOTICE
:
If a new configruation is loaded into the SMX system, the system LED lights
YELLOW
if the SMX
system is operated correctly. This signals an unvalidated application.
If the button Lock validation”
is enabled during an active connection to the module, the LED flashes
GREEN
.