Figure 171 properties window of DEM function
Parameters:
Permanently activated:
If this field is selected, the function i permanently enabled. The input connector of the block is
deleted.
Limit speed:
When the speed value that is given in this case is exceeded, the muting function is enabled. If the
activation is permanently disabled, additionally the status of the function block input is linked.
NOTICE
:
The limit speed also determines the maximum input values for the speed limit in the functions SLS,
SOS, SLI and SCA. The input values of the functions SLS, SOS, SLI and SCA must always be
lower than the muted speed limit.
Hysteresis:
To prevent a switching of the enabled function, a hysteresis value can be set.
Enabled function: speed thr hysteresis
Disabled function: speed threshold