384
Software • B&R Automation Device Interface (ADI) driver - Control Center
Automation PC 620 with 945GME N270 CPU board User's Manual V 1.10
Changing the UPS shutdown time when battery is low
Enter the
"Low Battery" shutdown time
in seconds. This is the amount of time that the UPS
will wait before shutting off the power supply when the battery level is low.
This prevents the UPS battery from becoming too discharged if the Windows UPS service is not
enabled and the UPS is therefore not turned off by the operating system.
If the UPS service is enabled, then the UPS will be turned off by the operating system when the
battery level is low, based on the Windows UPS service
Turn-off delay
additional UPS settings"). The
low battery shutdown time
will then be ignored.
10.4.7 Changing additional UPS settings
1) Open the
Control Center
in the
Control Panel
.
2) Select
UPS
tab.
3) Click on
Advanced
under
UPS settings
. This opens the following dialog box:
Information:
•
The low battery shutdown time must be set to at least 60 seconds, so that the
operating system has enough time to send the shutdown command to the
UPS when the battery level is low (normally occurs after approximately 30
seconds).
•
The low battery shutdown time can only be set in UPS firmware version 1.10
and later. UPS firmware version 1.08 always uses a turn off delay time of 180
seconds. UPS firmware versions earlier than 1.08 do not shut down
automatically when the battery level is low.
Figure 178: ADI Control Center - Advanced UPS settings
Summary of Contents for Automation PC 620
Page 2: ...2 Automation PC 620 with 945GME N270 CPU board User s Manual V 1 10 ...
Page 4: ...4 Automation PC 620 with 945GME N270 CPU board User s Manual V 1 10 ...
Page 6: ...6 Automation PC 620 with 945GME N270 CPU board User s Manual V 1 10 ...
Page 568: ...568 Appendix A Glossary Automation PC 620 with 945GME N270 CPU board User s Manual V 1 10 ...