7-8 Parameter Descriptions
MN761
7.2 Function Group1
Continued
Parameter #
Access
Parameter Name, Value Range, Description and Preset Value
RW
Electronic Thermal Level for 1 Minute
(Range: 50-150%)
Sets the maximum continuous motor current allowed for 1 minute as a % of
H33. Cannot be less than F52.
Preset Value:
150
Parameter is only displayed when F50=1.
RW
Electronic Thermal Level for Continuous
(Range: 50-150%)
Sets maximum continuous motor current allowed as a % of H33.
Cannot exceed F51.
Preset Value:
100
Parameter is only displayed when F30=2.
RW
Motor Cooling Method
(Range:
0- Cooled by fan connected directly to the shaft of the motor.
1- Cooled by fan powered by a separate motor.)
Sets the motor cooling method used.
Preset Value:
0
Parameter is only displayed when F30=2.
RW
Overload Warning Level
(Range: 30-150%)
Sets the alarm current level that activates a relay or digital output terminal
as a percentage of H33. Select one output terminal for this function (MO
or 30AC). For digital output, set I54=5. For relay output, set I55=5.
See also:
I54 and I55
Preset Value:
150
Current
Active Output
F54
t=Overload warning time
t
t
RW
Overload Warning Time
(Range: 0-30sec)
Sets the amount of time motor current greater than F54 is tolerated.
After this time an alarm is issued if the Overload continues.
Preset Value:
10
RW
Overload Trip Selection
(Range:
0- Off. Output is NOT turned off for overload.
1- On. Output is disabled (trip) and motor coasts to stop for overload.
Sets if the motor output is turned off when motor overload is detected.
Preset Value:
1
RW
Overload Trip Level
(Range: 30-200%)
Sets the motor current required to trigger an overload trip as a % of H33.
Preset Value:
180
Parameter is only displayed when F56=1.
RW
Overload Trip Time
(Range: 0-60sec)
Sets the amount of time motor current greater than F57 is tolerated.
After this time an overload trip is issued if the Overload continues.
Preset Value:
60
Parameter is only displayed when F56=1.
Summary of Contents for VS1SM
Page 1: ...Installation Operating Manual VS1SM Single Phase AC Drive 10 07 MN761...
Page 10: ...2 2 General Information and Ratings MN761...
Page 28: ...6 8 Using the Keypad MN761...
Page 57: ...MN761 Customizing for Your Application 8 1 Chapter 8 Customizing for Your Application...
Page 58: ...8 2 Customizing for Your Application MN761...
Page 63: ...MN761 Parameter Tables B 1 Appendix B Parameter Tables Refer to Chapter 7...
Page 64: ...B 2 Parameter Tables MN761 B 1 1 Basic Parameters Continued...
Page 69: ...Baldor District Offices...