MN761
Technical Specifications A-1
Appendix A
Technical Specifications
All specifications are subject to change without notice.
Input Ratings
Voltage
230
Voltage range
190-253
Phase
Single Phase
Frequency
50/60Hz
±
5%
Impedance
1% minimum from mains connection
Output Ratings
Horsepower
0.5-3 HP @ 230VAC
Overload Capacity
150% for 1 minute
Frequency
0-400Hz
Voltage
0 to maximum input voltage (RMS)
Protective Features
Trip
Over Voltage, Low Voltage, Over Current, Ground
Fault, Inverter Overheat, Motor Overheat, Output
Phase Open, Overload Protection, External Faults,
Communication Error, Loss of Speed Command,
Hardware Fault, Option Fault.
Stall Prevention
Over voltage suppression, over current suppression
External Output
LED trip condition indicators, 5 assignable logic
outputs, 2 assignable analog outputs
Short Circuit
Phase to phase, phase to ground
Electronic Motor Overload
Meets UL508C (
I
2
T)
Environmental
Conditions
Temperature
-10 to 40
°
C Derate 3% per degree C above 40 to
50
°
C maximum ambient temperature
Cooling
Forced air
Enclosure
IP20, NEMA 1 (optional)
Altitude
Sea level to 3300 Feet (1000 Meters)
Derate 2% per 1000 Feet (303 Meters) above 3300
Feet
Humidity
10 to 90% RH Non‐Condensing
Shock
1G
Vibration
0.5G at 10Hz to 60Hz
Storage Temperature
‐20 to +65
°
C
Duty Cycle
1.0
Summary of Contents for VS1SM
Page 1: ...Installation Operating Manual VS1SM Single Phase AC Drive 10 07 MN761...
Page 10: ...2 2 General Information and Ratings MN761...
Page 28: ...6 8 Using the Keypad MN761...
Page 57: ...MN761 Customizing for Your Application 8 1 Chapter 8 Customizing for Your Application...
Page 58: ...8 2 Customizing for Your Application MN761...
Page 63: ...MN761 Parameter Tables B 1 Appendix B Parameter Tables Refer to Chapter 7...
Page 64: ...B 2 Parameter Tables MN761 B 1 1 Basic Parameters Continued...
Page 69: ...Baldor District Offices...