7-28 Parameter Descriptions
MN761
7.4 I/O Group
Continued
Parameter #
Access
Parameter Name, Value Range, Description and Preset Value
RW
Fault Relay Output
(Range:
0- None
1- At Low Voltage Trip.
2- All trips other than Low Voltage.
3- All trips.
4- When setting H26 [Number of Auto-Restart Tries]
5- H26 and Low Voltage Trips.
6- H26 and All trips.
7- H26 and All trips.)
Sets the item that will be output by digital and relay outputs.
Preset Value:
2
RW
Inverter Station ID
(Range: 1-32)
Sets Inverter ID for RS485 Communication.
Preset Value:
1
RW
Baud Rate
(Range:
0- 1200 bps
1- 2400 bps
2- 4800 bps
3- 9600 bps
4- 19200 bps)
Sets the Baud Rate of RS485 Communication.
Preset Value:
3
RW
Drive Mode After Loss of Speed Command
(Range:
0- Continue operation at last frequency before command was lost.
1- Coast to stop.
2- Deceleration to stop.)
Sets the action during loss of speed reference command. Speed reference
command by V1 or I terminal or by communication option.
Preset Value:
RW
Wait Time after Loss of Speed Command
(Range: 0.1-120sec)
Sets the delay after loss of speed reference before I62 is active. If the
Speed Reference command is still lost after this delay, I62 mode occurs.
Preset Value:
1.0
Summary of Contents for VS1SM
Page 1: ...Installation Operating Manual VS1SM Single Phase AC Drive 10 07 MN761...
Page 10: ...2 2 General Information and Ratings MN761...
Page 28: ...6 8 Using the Keypad MN761...
Page 57: ...MN761 Customizing for Your Application 8 1 Chapter 8 Customizing for Your Application...
Page 58: ...8 2 Customizing for Your Application MN761...
Page 63: ...MN761 Parameter Tables B 1 Appendix B Parameter Tables Refer to Chapter 7...
Page 64: ...B 2 Parameter Tables MN761 B 1 1 Basic Parameters Continued...
Page 69: ...Baldor District Offices...