Parameter Descriptions 7-15
7.3 Function Group2
Continued
Parameter #
Access
Parameter Name, Value Range, Description and Preset Value
RW
Proportional (P) Gain for PID
(Range: 0-999.9%)
Sets the P Gain for the PID Controller.
If P Gain is set to 50%, 50% of the error value will be output.
Preset Value:
300
Parameter is only displayed when H40=2 or 3.
RW
Integral Time (I) Gain for PID
(Range: 0.1-32.0sec)
Sets the I Gain for the PID Controller, the time needed to output the
accumulated error value.
Set the time required to output 100% when the error value is 100%.
For example, if H52=1 sec, 100% is output in 1 second.
Preset Value:
1.0
Parameter is only displayed when H40=2 or 3.
RW
Differential Time (D) Gain for PID
(Range: 0-30.0sec)
Sets the D Gain for the PID Controller.
This is the output value corresponding to the variation of the error.
Preset Value:
0.0
Parameter is only displayed when H40=2 or 3.
RW
Feed Forward (F) Gain for PID
(Range: 0-999.9%)
Sets the F Gain for the PID Controller. This is the gain to add the target
value to the PID controller output.
Preset Value:
0.0
Parameter is only displayed when H40=2 or 3.
RW
PID Output Frequency Limit
(Range: 0.1-400Hz)
Sets the output frequency limit through the PID Controller.
Must be set within the limits of F21and F23.
Preset Value:
60.00
Parameter is only displayed when H40=2 or 3.
Summary of Contents for VS1SM
Page 1: ...Installation Operating Manual VS1SM Single Phase AC Drive 10 07 MN761...
Page 10: ...2 2 General Information and Ratings MN761...
Page 28: ...6 8 Using the Keypad MN761...
Page 57: ...MN761 Customizing for Your Application 8 1 Chapter 8 Customizing for Your Application...
Page 58: ...8 2 Customizing for Your Application MN761...
Page 63: ...MN761 Parameter Tables B 1 Appendix B Parameter Tables Refer to Chapter 7...
Page 64: ...B 2 Parameter Tables MN761 B 1 1 Basic Parameters Continued...
Page 69: ...Baldor District Offices...