Parameter Descriptions 7-27
7.4 I/O Group
Continued
Parameter #
Access
Parameter Name, Value Range, Description and Preset Value
RW
Analog Output Function
(Range: 0-3)
0- Output Frequency. (Range=Min to Max frequency).
1- Output Current. (Range 0- 150%).
2- Output Voltage. (Range 0-282VAC).
3- DC Link Voltage. (Range 0-400VDC).
Sets the parameter value represented by the 0-10VDC Analog output.
Preset Value:
0
RW
Analog Output Level
(Range: 10-200%)
Adjusts the gain for the parameter range can be adjusted to be within the
0-10VDC output level.
Preset Value:
100
RW
Frequency Detection Level
(Range: 0-400Hz)
Used when I54=0-4 or I55=0-4.
Preset Value:
30.00
RW
Frequency Detection Bandwidth
(Range: 0-400Hz)
Used when I54=0-4 or I55=0-4.
Preset Value:
10.00
RW
Digital
Output Function
(Range:
0- FDT-1.
1- FDT-2.
2- FDT-3.
3- FDT-4.
4- FDT-5.
5- Overload (OLt).
6- Inverter Overload (IOL).
7- Motor Stall (STALL).
8- Over Voltage Trip (OV).
9- Low Voltage Trip (LV).
10- Inverter Overheat (OH).
11- Command Loss.
12- During Run.
13- During Stop.
14- During Constant Run.
15- During Speed Searching.
16- Wait Time for Run Signal Input.
17- Fault Relay Output. )
Sets the parameter value represented by the digital and relay outputs.
If I54=17, the outputs are active by the condition set in I56.
Preset Value:
I54=12, I55=17
Summary of Contents for VS1SM
Page 1: ...Installation Operating Manual VS1SM Single Phase AC Drive 10 07 MN761...
Page 10: ...2 2 General Information and Ratings MN761...
Page 28: ...6 8 Using the Keypad MN761...
Page 57: ...MN761 Customizing for Your Application 8 1 Chapter 8 Customizing for Your Application...
Page 58: ...8 2 Customizing for Your Application MN761...
Page 63: ...MN761 Parameter Tables B 1 Appendix B Parameter Tables Refer to Chapter 7...
Page 64: ...B 2 Parameter Tables MN761 B 1 1 Basic Parameters Continued...
Page 69: ...Baldor District Offices...