7-12 Parameter Descriptions
MN761
7.3 Function Group2
Continued
Parameter #
Access
Parameter Name, Value Range, Description and Preset Value
RW
Auto
Restart
(Range:
0- Off. Motor will not start immediately when fault condition is reset.
1- On. Motor will start acceleration when fault condition is reset)
Sets whether the motor will automatically start after a fault condition is reset
and a Run command is present. After the fault is reset, with drV=1 or 2
and either Forward Run or Reverse Run input is active, the motor will
start immediately.
Preset Value:
0
Reset
Frequency
H21=0
H21=1
Run
command
RW
Speed Search
(Range:
0- No speed search.
1- Normal search.
2-
After Fault.
3- Normal search, After Fault,
4-
After Fault,
After Power Failure,
5- Normal search, After Fault,
After Power Failure,
6-
After Fault,
After Power Failure,
7- Normal search, After Fault,
After Power Failure,
8-
Power on start.
9- Normal search, After Fault,
Power on start.
10-
After Fault,
Power on start.
11- Normal search, After Fault,
Power on start.
12-
After Fault,
After Power Failure, Power on start.
13- Normal search,
After Power Failure, Power on start.
14-
After Fault,
After Power Failure, Power on start.
15- Normal search, After Fault,
After Power Failure, Power on start.
Note: On power start if H20=1)
Note: Normal search done is first even when others are also selected.
Helps prevent faults when attempting to start a running motor.
(After power outage while motor is coasting).
Preset Value:
0
RW
Current Level During Speed Search
(Range: 80-200%)
Sets the motor current during speed search as a % of H33.
Preset Value:
100
RW
P Gain During Speed Search
(Range: 0-9999)
Sets the PI Controller Proportional Gain used during Speed Search.
Preset Value:
100
Summary of Contents for VS1SM
Page 1: ...Installation Operating Manual VS1SM Single Phase AC Drive 10 07 MN761...
Page 10: ...2 2 General Information and Ratings MN761...
Page 28: ...6 8 Using the Keypad MN761...
Page 57: ...MN761 Customizing for Your Application 8 1 Chapter 8 Customizing for Your Application...
Page 58: ...8 2 Customizing for Your Application MN761...
Page 63: ...MN761 Parameter Tables B 1 Appendix B Parameter Tables Refer to Chapter 7...
Page 64: ...B 2 Parameter Tables MN761 B 1 1 Basic Parameters Continued...
Page 69: ...Baldor District Offices...