7-10 Parameter Descriptions
MN762S
7.3.2 Parameter Group 3 – PID Control
Table 7-3 Parameter Group 3 - PID Control
Par No.
Description
Range
Units
Default
Explanation
P3-01
Proportional gain
0.1 to 30.0
-
2.0
PID Controller Proportional
Gain. Higher values provide
a greater change in the
drive output frequency in
response to small changes
in the feedback signal. Too
high a value can cause
instability.
P3-02
Integral time
constant
0.0 to 30.0
Seconds
1.0
PID Controller Integral
Time. Larger values
provide a more damped
response for systems
where the overall process
responds slowly.
P3-03
Differential time
constant
0.00 to 1.0
Seconds
0.00
PID Differential Time
Constant
P3-04
PID operating mode
0: Direct
1: Inverse
-
0
Direct operation – Motor
speed increases with an
increase in the feedback
signal.
Inverse Operation – Motor
speed decreases with an
increase in the feedback
signal.
P3-05
PID Set point /
reference select
0: Digital
1: Analog
-
0
Selects the source for the
PID Reference / Setpoint
0: P3-06 is used
1: Bipolar analog input is
used
P3-06
PID digital reference
0.0 to 100.0
%
0.0
Sets the preset digital PID
reference / set point.
P3-07
PID controller high
limit output
P3-08 to 100.0
%
100
Limits the maximum
value output from the PID
controller.
P3-08
PID controller low
limit output
0 to P3-07
%
0
Limits the minimum output
from the PID controller
Summary of Contents for VS1MXS51
Page 1: ...03 11 Installation Operating Manual MN762S VS1MXS AC Extreme Duty Microdrive...
Page 28: ...5 10 Control Wiring MN762S...
Page 58: ...7 24 Parameter Descriptions MN762S...
Page 60: ...8 2 Customizing Your Application MN762S...
Page 80: ...D 2 Options and Kits MN762S...
Page 85: ......
Page 86: ......