5-8 Control Wiring
MN762S
5.3.3 PI Control Mode (P1-07 = 3)
Table 5-5 Parameter P1-08 Control of Digital Inputs when P1-07 = 3
P1-08
Digital In 1
(Term 2)
Digital In 2
(Term 3)
Digital In 3
(Term 4)
Analog Input
(Term 6)
0, 10, 13,
16, 18
Open: Stop
Closed: Run
No Function
Analog input 2
Bipolar analog input
11
Open: Stop
Closed: Run
Open: PID control
Closed: Preset Speed 1
External trip input
Bipolar analog input
Open: Trip
Closed: No Trip
12
Open: Stop
Closed: Run
Open: Preset Speed 1
Closed: PID control
External trip input
Bipolar analog input
Open: Trip
Closed: No Trip
17
Open: Stop
Closed: Run
Open: PID control
Closed: Bipolar analog
ref
Analog input 2
Bipolar analog input
19
Open: Stop
Closed: Run
Open: PID control
Closed: Analog input 2
Analog input 2
Bipolar analog input
20, 21
Open: Stop
Closed: Run
Digital Output:
Drive Healthy = +24V
Analog input 2
Bipolar analog input
22
Open: Stop
Closed: Run
Digital Output:
Drive Healthy = +24V
External trip input
Bipolar analog input
Open: Trip
Closed: No Trip
Note:
When P3-05 = 1, Bipolar analog input controls PID set point. The feedback must then be connected
to Analog input 2 and P3-10 must be set to 0 (Default setting). The external trip input only functions
when the feedback source is the Bipolar analog input (P3-10 = 1).
Summary of Contents for VS1MXS51
Page 1: ...03 11 Installation Operating Manual MN762S VS1MXS AC Extreme Duty Microdrive...
Page 28: ...5 10 Control Wiring MN762S...
Page 58: ...7 24 Parameter Descriptions MN762S...
Page 60: ...8 2 Customizing Your Application MN762S...
Page 80: ...D 2 Options and Kits MN762S...
Page 85: ......
Page 86: ......