Parameter Descriptions 7-21
MN762S
Par
No.
Description
Range
Units
Default
Explanation
P6-10
Brake Chopper
Duty Cycle
when Under
Temperature
0.0…20.0
%
2.0
This parameter defines the duty
cycle applied to the brake chopper
while the drive is in an under
temperature trip state. A Brake
resistor can be mounted to the
drive heat sink, and used to warm
the drive until the correct operating
temperature is reached.
This parameter should be
used with extreme care, as
incorrect adjustment may result
in exceeding the rated power
capacity of the resistor. External
thermal protection for the resistor
should always be used to avoid
this risk.
P6-11
Preset Speed
Run Time On
Enable
0.0..600.0
S
0.0
Defines a time period for which,
following an enable signal being
applied to the drive, the drive will
run at the speed programmed
in Preset Speed 7 (P2-07). This
feature can be used on pumps to
provide a reverse spin on start up,
to avoid potential blockages.
P6-12
Preset Speed
Run Time on
Disable
0.0..600.0
S
0.0
Defines a time period for which,
following removal of the enable
(Run) signal and the drive ramping
to standstill, the drive will then
operate at the speed set in Preset
Speed 8 (P2-08). This feature
can be used in applications such
as underground PCP pumps to
provide unwind of the driveshaft on
stopping.
Table 7-7 Application Specific Parameters Continued
Summary of Contents for VS1MXS51
Page 1: ...03 11 Installation Operating Manual MN762S VS1MXS AC Extreme Duty Microdrive...
Page 28: ...5 10 Control Wiring MN762S...
Page 58: ...7 24 Parameter Descriptions MN762S...
Page 60: ...8 2 Customizing Your Application MN762S...
Page 80: ...D 2 Options and Kits MN762S...
Page 85: ......
Page 86: ......