Control Wiring 5-7
MN762S
P1-08
Digital In 1
(Term 2)
Digital In 2
(Term 3)
Digital In 3
(Term 4)
Analog Input
(Term 6)
19
Open: Stop
Open: Digital speed ref
Analog input 2
Open: Forward
Closed: Run
Closed: Analog input 2 ref
Closed: Reverse
20, 21
Open: Stop
Digital Output:
Open: Digital speed ref
Open: Forward
Closed: Run
Drive Healthy = +24V
Closed: Preset speed 1
Closed: Reverse
22
Open: Stop
Closed: Run
Digital Output:
Drive Healthy = +24V
External trip input
Open: Forward
Closed: Reverse
Open: Trip
Closed: No Trip
Notes:
By default, if the enable signal is present the drive will not Enable until the START button is
pressed. To automatically enable the drive when the enable signal is present set P2-19 = 2 or 3.
This disables the use of the START & STOP buttons.
In keypad mode, the speed can be adjusted using the UP & DOWN keys on the built in keypad, or a
remote mounted keypad, in addition to push buttons connected to the digital inputs.
The reverse input only functions under the following conditions:
- P1-07 = 1, P2-19 = 2 or 3. P2-35 must not be 2 or 3.
- P1-07 = 2. P 2-35 must not be 2 or 3.
The external trip input can be used to connect a motor thermistor by connecting between
terminals 1 and 4
When P1-0 7 = 2 , the direction of motor can be reversed by:
- pressing the START button.
- closing the reverse input (When using a setting of P1-08 that includes this function).
- using a negative speed reference (e.g. select a preset speed of -10Hz).
Since all of these functions can be active at once, care must be taken to ensure the motor always
turns in the correct direction.
Table 5-4 Parameter P1-08 Control of Digital Inputs when P1-07=1 or 2 Continued
Summary of Contents for VS1MXS51
Page 1: ...03 11 Installation Operating Manual MN762S VS1MXS AC Extreme Duty Microdrive...
Page 28: ...5 10 Control Wiring MN762S...
Page 58: ...7 24 Parameter Descriptions MN762S...
Page 60: ...8 2 Customizing Your Application MN762S...
Page 80: ...D 2 Options and Kits MN762S...
Page 85: ......
Page 86: ......