Control Wiring 5-1
MN762S
Chapter 5
Control Wiring
5.1 Control Board Connections
Analog and Digital input and output connections are made at the Control Wiring Terminals shown in
Figure 5-1.
Control wire connections can be made using shielded twisted pair #18 AWG (0.8mm2) wire minimum.
The cable must also have an overall shield and not exceed 100 feet (30m) in length. Control wire
cables must be separated from power wiring. Separate parallel runs of control cables and power
cables by at least 3”. Cross power wires at right angles only. Insulate or tape ungrounded end of
shields to prevent contact with other conductors or ground.
The Control Wiring Terminals are prewired to allow front panel Potentiometer and FWD-Off-Rev switch
operation. Simply remove these terminal connections (pins 1 to 7) and connect external devices as
desired. These terminals are described in Table 5-1.
Figure 5-1 Control Terminals
Red
Blu
Yel
Grn
Wht
Blk
Front
Panel
Potentiometer
Front
Panel
FWD-REV
Switch
Control Wiring
Terminals
Only on
Switched
version
Table 5-1 Control Terminal Descriptions
Terminal
Signal Description
1
+24VDC (@ 100 mA)
2
Digital In1
3
Digital In2
4
Digital In3 / Analog In2
5
+10VDC (@ 10 mA) Reference for Potentiometer (1kohm minimum)
6
Analog In1 / Digital In4
7
Common (terminals 7 & 9 are connected)
8
Analog Output (0-10VDC @ 10mA) / Digital Output (0-24VDC)
9
Common (terminals 7 & 9 are connected)
10
Relay Common
11
Relay N.O. Contact (rated 250VAC@5A; 30VDC@5A)
Summary of Contents for VS1MXS51
Page 1: ...03 11 Installation Operating Manual MN762S VS1MXS AC Extreme Duty Microdrive...
Page 28: ...5 10 Control Wiring MN762S...
Page 58: ...7 24 Parameter Descriptions MN762S...
Page 60: ...8 2 Customizing Your Application MN762S...
Page 80: ...D 2 Options and Kits MN762S...
Page 85: ......
Page 86: ......