6-2 Using the Keypad
MN762S
6.2 Using the REV/0/FWD Selector Switch
(Switched version only)
By adjusting the parameter settings the VS1MXS can be configured for multiple applications and not
just for Forward or Reverse. This could typically be for Hand/Off/Auto applications (also known and
Local/Remote) for HVAC and pumping industries.
Table 6-2 REV/0/FWD Switch Controls
Switch Position
Parameters
Notes
P1-07
P1-08
Notes
STOP
STOP
Run
Forward
0
0
Factory Default Configuration
Preset Speed
1
STOP
Run
Forward
0
0
Preset Speed 1 provides a ‘Jog’
Speed
Run Reverse
STOP
Run
Forward
0
7, 8, 9,
10
Run in Speed
Control
STOP
Run in PID
Control
3
17
In Speed Control, POT controls
speed
In PID Control, POT controls set point
Run in Speed
Control
STOP
Run in PID
Control
3
11
In Speed Control, P2-1 sets the
Preset Speed
In PID Control, pot controls set point
Run in Hand
STOP
Run in
Auto
4
17
Hand – Speed reference from Pot
Auto – Speed Reference from
Modbus
Run in Hand
STOP
Run in
Auto
4
17
Hand – Speed reference from Preset
Speed 1
Auto – Speed Reference from
Modbus
6.3 Changing Parameters
To change a parameter value press and hold the ENT/PROG key for > 2 seconds while the drive
displays
. The display changes to
, indicating parameter 01. Press and release the ENT/
PROG key to display the value of this parameter.
Use the UP and DOWN arrow keys to change to the required value. Press and release
the ENT/PROG key once more to store the change. Press and hold the ENT/PROG key for > 2 second
to return to operational mode. The display shows
if the drive is stopped or the real-time
information (for example speed) if the drive is running.
OFF
FWD
REV
OFF
FWD
REV
OFF
FWD
REV
PROG
ENT
Summary of Contents for VS1MXS51
Page 1: ...03 11 Installation Operating Manual MN762S VS1MXS AC Extreme Duty Microdrive...
Page 28: ...5 10 Control Wiring MN762S...
Page 58: ...7 24 Parameter Descriptions MN762S...
Page 60: ...8 2 Customizing Your Application MN762S...
Page 80: ...D 2 Options and Kits MN762S...
Page 85: ......
Page 86: ......