AXP1440 Shelf Installation
AXP1440 Installation and Use (6806800H23U)
95
5.8
Power Cable Termination
Custom lugs are used with large gauge wires for up to 80 Amps DC (4 AWG) when connecting
to the PEM. These are shipped with the product.The lugs are angled to allow the cables to be
dressed below the cable management tray, thus protecting the circuit breakers from
accidental tripping.
Wire
Signal
Earth Ground
PE GND (Primary Earth Ground)
Input power
-48 VDC nominal to -60 VDC
Return
-48 VDC RETURN
Figure 5-4. DC Power Connection Detail
OFF
ON
OFF
ON
-48 VDC RTN
-48 VDC
VDC RTN
-48 VDC