Safety Notes
26
AXP1440 Installation and Use (6806800H23U
)
This equipment shall be located in the same immediate area (such as, adjacent cabinets) as any
other equipment that has a connection between the earthed conductor of the same DC supply
circuit and the earthing conductor, and also the point of earthing of the DC system. The DC
system shall not be earthed elsewhere.
The DC supply source shall be located within the same premises as this equipment.
Switching or disconnecting devices shall not be in the earthed circuit conductor between the
DC source and the point of connection of the earthing electrode conductor.
French translation: Cet appareil est conçu pour permettre le raccordement du conducteur relié
à la terre du circuit d'alimentation c.c. au conducteur de terre de l'appareil. Pour ce
raccordement, toutes les conditions suivantes doivent être respectées:
Ce matériel doit être raccordé directement au conducteur de la prise de terre du circuit
d'alimentation c.c. ou à une tresse de mise à la masse reliée à une barre omnibus de terre
laquelle est raccordée à l'électrode de terre du circuit d'alimentation c.c.
Les appareils dont les conducteurs de terre respectifs sont raccordés au conducteur de terre du
même circuit d'alimentation c.c. doivent être installés à proximité les uns des autres (p.ex.,
dans des armoires adjacentes) et à proximité de la prise de terre du circuit d'alimentation c.c.
Le circuit d'alimentation c.c. ne doit comporter aucune autre prise de terre.
La source d'alimentation du circuit c.c. doit être située dans la même pièce que le matériel. - Il
ne doit y avoir aucun dispositif de commutation ou de sectionnement entre le point de
raccordement au conducteur de la source d'alimentation c.c. et le point de raccordement à la
prise de terre.
System Overheating
If you reduce the fan speed, the system temperature will rise.
Constantly control the system temperature once you have reduced the fan speed.
While operating the system ensure that the environmental and power requirements are met.
Injuries or Short Circuits
Blade or Power Supply
In case the ORing diodes of the blade fail, the blade may trigger a short circuit between input
line A and input line B so that line A remains powered even if it is disconnected from the power
supply circuit (and vice versa).
Summary of Contents for AXP1440
Page 1: ...AXP1440 Installation and Use P N 6806800H23U October 2018...
Page 8: ...6 AXP1440 Installation and Use 6806800H23U Contents...
Page 10: ...List of Figures 8 AXP1440 Installation and Use 6806800H23U...
Page 12: ...List of Tables 10 AXP1440 Installation and Use 6806800H23U...
Page 20: ...AXP1440 Installation and Use 6806800H23U About this Manual 18 About this Manual...
Page 79: ...Site Preparation AXP1440 Installation and Use 6806800H23U 77 Figure 3 4 Planning Checklist 2...
Page 80: ...Site Preparation 78 AXP1440 Installation and Use 6806800H23U...
Page 108: ...AXP1440 Shelf Installation 106 AXP1440 Installation and Use 6806800H23U...
Page 152: ...Shelf Management Alarm Module 150 AXP1440 Installation and Use 6806800H23U...
Page 155: ...1...