Site Preparation
AXP1440 Installation and Use (6806800H23U)
75
3.2.8
Airflow Requirements
The AXP1440 provides fault tolerant cooling to front-mounted AdvancedTCA blades and to
rear transition modules based on one front and one rear maintainable intelligent fan trays with
six fans per tray.
Fan trays are mounted in the shelf top and bottom. The figure below shows the general airflow
for the system.
NOTES: The cooling subsystem is compliant to CP-TA B.4. The cooling system provides for
greater than 40 CFM for the front blade and 5.0 CFM for the RTM.
The actual cooling performance depends on the slot population and the heat sink
design of installed blades and should be validated based on the used configuration.
The distance to other equipment must be sufficient to avoid an overheating of the
system.
The cooling subsystem is designed to provide 31.1 CFM in the front and presence of
any single cooling failure.
Figure 3-2. Shelf Airflow
RTM
Outlet Plenum
Chassis
Front
Chassis
Rear
Chassis
Exhaust
Air Flow
Lower Front Air Intake
Lower FTMs
Upper FTM
Room
Ambient
Air Flow
PEM
Exhaust
Summary of Contents for AXP1440
Page 1: ...AXP1440 Installation and Use P N 6806800H23U October 2018...
Page 8: ...6 AXP1440 Installation and Use 6806800H23U Contents...
Page 10: ...List of Figures 8 AXP1440 Installation and Use 6806800H23U...
Page 12: ...List of Tables 10 AXP1440 Installation and Use 6806800H23U...
Page 20: ...AXP1440 Installation and Use 6806800H23U About this Manual 18 About this Manual...
Page 79: ...Site Preparation AXP1440 Installation and Use 6806800H23U 77 Figure 3 4 Planning Checklist 2...
Page 80: ...Site Preparation 78 AXP1440 Installation and Use 6806800H23U...
Page 108: ...AXP1440 Shelf Installation 106 AXP1440 Installation and Use 6806800H23U...
Page 152: ...Shelf Management Alarm Module 150 AXP1440 Installation and Use 6806800H23U...
Page 155: ...1...