AXP1440 Shelf Installation
90
AXP1440 Installation and Use (6806800H23U
)
5.3.3
Mounting Options and Stabilization
The AXP1440 is designed to be mounted in an equipment rack while maintaining conformance
to the NEBS 24" deep lineup and the ETSI 600mm deep lineup standards for
telecommunication equipment. For increased stability, we recommend that the rack is
securely mounted to the floor, or if using stabilizing devices make sure they are installed and
extended.
Figure 5-2. Shelf Airflow Diagram
RTM
Outlet Plenum
Chassis
Front
Chassis
Rear
Chassis
Exhaust
Air Flow
Lower Front Air Intake
Lower FTMs
Upper FTM
Room
Ambient
Air Flow
PEM
Exhaust