AXP1440 Shelf Installation
92
AXP1440 Installation and Use (6806800H23U
)
5.4.1
23" EIA Rack/Cabinet
Procedure - Install in EIA Rack
Front mounting brackets are required to attach the shelf to an EIA 23" frame.
1. Locate the standard mounting hole and slot locations on the front mounting flanges
on the AXP1440 shelf.
2. Fasten the mounting brackets to the back side of the front chassis flanges using M6
screws x 12mm at each of the 5 locations.
3. Be sure to mount the shelf with metal screws or bolts that give a good electrical
connection between the screws or bolts and the mounting surface.
4. Tighten all screws using a torque setting of 4.01 to 4.35 N-m.
NOTE: Failure to observe proper grounding practices may cause a variety of noise,
electrostatic discharge, and RFI (Radio Frequency Interference) problems.
5.4.2
600mm ETSI Rack/Cabinet
Procedure - Install in 600mm ETSI Rack
The shelf mounts directly from the integrated flange on the front of the shelf.
1. Locate the standard mounting hole and slot locations on the front integrated
mounting flanges on the AXP1440 shelf.
2. Fasten the mounting brackets to the back side of the front chassis flanges using M6
screws x 12mm at each of the 5 locations.
3. Be sure to mount the shelf with metal screws or bolts that give a good electrical
connection between the screws or bolts and the mounting surface.
Do not mount a single shelf at the top of the rack. A top-heavy rack can tip, causing
damage to equipment and injury to personnel.
Do not use the FTM handles or PEM handles for lifting the shelf.
Make sure you have the appropriate equipment to safely lift and mount the shelf
securely. To avoid personal injury or damage to the equipment, use two persons for the
installation procedure.
Summary of Contents for AXP1440
Page 1: ...AXP1440 Installation and Use P N 6806800H23U October 2018...
Page 8: ...6 AXP1440 Installation and Use 6806800H23U Contents...
Page 10: ...List of Figures 8 AXP1440 Installation and Use 6806800H23U...
Page 12: ...List of Tables 10 AXP1440 Installation and Use 6806800H23U...
Page 20: ...AXP1440 Installation and Use 6806800H23U About this Manual 18 About this Manual...
Page 79: ...Site Preparation AXP1440 Installation and Use 6806800H23U 77 Figure 3 4 Planning Checklist 2...
Page 80: ...Site Preparation 78 AXP1440 Installation and Use 6806800H23U...
Page 108: ...AXP1440 Shelf Installation 106 AXP1440 Installation and Use 6806800H23U...
Page 152: ...Shelf Management Alarm Module 150 AXP1440 Installation and Use 6806800H23U...
Page 155: ...1...