AXP1440 Shelf Installation
AXP1440 Installation and Use (6806800H23U)
93
4. Tighten all screws using a torque setting of 4.01 to 4.35 N-m.
NOTE: Failure to observe proper grounding practices may cause a variety of noise,
electrostatic discharge, and RFI (Radio Frequency Interference) problems.
5.5
Grounding the Shelf
Use a 2 AWG wire with a 2-hole copper lug and connect directly to the earth ground point
located on the right side of the back of the shelf; connect the other end of the wire to a reliable
earth ground. Use the torque setting required by the connector supplier. The 2-hole lug
prevents rotation of the lug and ensures a permanent bonding of ground to the shelf. The dual
hole mount accepts 1/4 #20 screws. Use Panduit LCC2-14AW-Q 2-hole lug or equivalent.
5.6
Shelf Ground Configuration
The AXP1440 shelf was tested in the default configuration of logic ground and shelf ground
connected and does not connect -48VDC Return with Shelf Ground. The system has been
tested in the default configuration and complies with safety and regulatory standards. As a
compliant AdvancedTCA shelf, the AXP1440 allows system integrator at their own discretion
to remove the mechanism which connects Logic Ground to Shelf Ground and install the
mechanism that connects -48VDC Return to Shelf Ground. If the system integrator exercises
Figure 5-3. Placement of Grounding Lug
4437 0706
15
Back of Shelf
Summary of Contents for AXP1440
Page 1: ...AXP1440 Installation and Use P N 6806800H23U October 2018...
Page 8: ...6 AXP1440 Installation and Use 6806800H23U Contents...
Page 10: ...List of Figures 8 AXP1440 Installation and Use 6806800H23U...
Page 12: ...List of Tables 10 AXP1440 Installation and Use 6806800H23U...
Page 20: ...AXP1440 Installation and Use 6806800H23U About this Manual 18 About this Manual...
Page 79: ...Site Preparation AXP1440 Installation and Use 6806800H23U 77 Figure 3 4 Planning Checklist 2...
Page 80: ...Site Preparation 78 AXP1440 Installation and Use 6806800H23U...
Page 108: ...AXP1440 Shelf Installation 106 AXP1440 Installation and Use 6806800H23U...
Page 152: ...Shelf Management Alarm Module 150 AXP1440 Installation and Use 6806800H23U...
Page 155: ...1...