134
CS175-275-575-875 Installation Guide
1
2
3
4
5
6
7
8
On: disables on-board 8 zones.
On: force default configuration for zone types to be used.
On: disables bypass reports for force arm.
On: enables resetting of tamper memory by a master code.
On: enables 2-wire smoke.
On: sets 25VA transformer.
On: enables Fire to Open / Last to Close.
On: enables Summer / Wintertime option.
Seg#3 (Circle numbers to program)
1
2
3
4
5
6
7
8
On: Box Tamper report enabled.
On: Mains Fail reporting enabled.
On: Low Battery reporting enabled.
On: Aux. Power Overcurrent report enabled.
On: Siren Supervision report enabled.
On: Telephone Line Cut report enabled.
Reserved
On: Expander Trouble reporting enabled.
Seg#4 (Circle numbers to program)
1
2
3
4
5
6
7
8
Failure To Communicate report enabled.
Log Full report enabled.
Autotest report enabled.
Start and End Programming report enabled.
End Download report enabled.
Sensor Low Battery report enabled.
Sensor Missing report enabled.
Reserved
Seg#5 (Circle numbers to program)
1
2 -8
Lost Clock service LED enabled.
Reserved.
52
System
timers
Seg#1 Dynamic Battery Test duration (0-255 minutes)
0
Seg#2 Mains Failure report delay (0-255 minutes)
5
Seg#3 Power Up Delay (0-60 seconds)
0
Seg#4 Internal Siren Time (1-255 minutes)
8
Seg#5 Telephone Line Cut delay (0-255 seconds)
0
Seg#6 B-alarm timer
5
Seg#7 Chime Time in 50 mS increments (0-255)
3
Seg#8 Fire Alarm Verification Time (120-255 sec.)
0
Seg#9 Zone Activity Monitor (0-255 Days)
0
Seg#10 Double Knock Time (0-255 minutes)
0
Seg#11 Double Knock Open Time (0-255 sec.)
Seg#12 External Siren time (1-255 minutes)
Seg13 – 14 Reserved
53
Special
features
Seg#1 (Circle numbers to program)
1
2
3
4
5-8
Enables six digit code option. All arm/disarm/Go to program codes require six digits
Requires valid user code entry for -9-8 and -9-9 functions to work.
Reserved.
Enable Walk-Test Mode.
Reserved.
54
Go to program code
1-2-7-8-0-0
55
Go to program code partition and authorization
Seg#1 (Circle numbers to program)
1
2
3
4
5
6
7
8
Reserved
Enables Go to program code as an arm only code.
Enables Go to program code as an arm only after closing.
Enables Go to program code as a master arm/disarm code (can change user codes)
Enables Go to program code as an arm/disarm code.
Enables Go to program code to bypass zones.
Enables Go to program code opening and closing reports.
Reserved