CS175-275-575-875 Installation Guide
Location 51
System options (five segments, FSD)
This location is used to enable various system feature and reporting options.
Segment 1
1
On: zone restores are delayed until siren timeout.
2
On: enables battery presence test (every 10 seconds).
3
On: dynamic battery test is performed at arming.
4
On: enables manual bell test.
5
On: enables manual communicator test.
6
On: enables box tamper input.
7
On: clock uses internal crystal.
8
On: disable temporal siren on fire.
Segment 2
1
On: disables on-board 8 zones.
2
On: forces default configuration for zone types to be used.
3
On: disables report bypass on force arm.
4
On: enables resetting of tamper memory by a master code
5
On: enables 2-wire smoke detectors to be used.
6
On: sets for 25 VA transformer.
7
On: enables first to open / last to close.
8
On: enables summer / winter time option.
Segment 3
1
On: enables box tamper report.
2
On: enables mains fail report.
3
On: enables low battery report.
4
On: enables aux. power overcurrent report.
5
On: enables siren supervision report.
6
On: enables telephone line cut report.
7
Reserved
8
On: enables expander trouble reporting.
Segment 4
1
On: enables fail to communicate report.
2
On: enables log full report.
3
On: enables autotest report.
4
On: enables start/end programming report.