Figure. 5.5.1. - 122. Group changing example sequence with pulse control only or with pulses and static signal.
Figure. 5.5.1. - 123. Second group changing example sequence with pulse control only or with pulses and static signal.
Settings and signals
Settings of the setting group control function includes the amount of available setting groups, selection
of force change enable and forced setting group selection. If the setting group is forced to change it
requires that the corresponding setting group is enabled and the force change is activated. After this
the setting group can be set from communications or from HMI to any available group. In case if the
setting group control is applied with steady state signals right after force setting group parameter is
released application shall take control of the setting group selection.
Table. 5.5.1. - 96. Settings of the SGS function.
Name
Range
Step
Default
Description
Used
setting
groups
0:SG1
1:SG1...2
2:SG1...3
3:SG1...4
4:SG1...5
5:SG1...6
6:SG1...7
7:SG1...8
-
0:SG1
Selection of activated setting groups in the application. If setting group is enabled
it cannot be controlled to active. When enabling new setting groups the activated
setting groups shall copy values from the SG1. Default setting is that only SG1 is
active.
Force
SG
change
enabled
0:Disabled
1:Enabled
-
0:Disabled
Setting of force setting group change either enabled or disabled. This setting has
to be active before the setting group can be changed remotely or from local HMI.
This parameter is overriding local control of the setting groups and is not time
dependable which means that in user activation this override shall be on until it is
disabled by user again.
Force
SG
change
0:none
1:SG1
2:SG2
3:SG3
4:SG4
5:SG5
6:SG6
7:SG7
8:SG8
-
0:none
Selection of override setting group. After force SG change is enabled any of the
con gured setting groups can be override on to the device. This control is always
based on pulse operating mode and also requires that the setting group selected
is speci cally controlled to “On” after force SG is disabled if there is no other
controls the last set SG shall remain active.