Milliamp outputs
Up to two independent milliamp option cards are supported. Each card has 4 milliamp -outputs and
one milliamp -input. If the IED has milliamp option card, enable mA-outputs by selecting:
Control
→
Device IO
→
mA Outputs
:
Figure. 5.5.4. - 131. Milliamp outputs are activated two at the time, channel 1&2 / channel 3&4 activation. Option card order
code is “I”.
Table. 5.5.4. - 107. Main settings of the mA outputs
Name
Range
Default
Description
mA option card 1
Enable mA Out Channels 1&2
0:Disabled
1:Enabled
0:Disabled
Enables mA output cards outputs.
Enable mA Out Channels 3&4
mA option card 2
Enable mA Out Channels 5&6
0:Disabled
1:Enabled
0:Disabled
Enables mA output cards outputs.
Enable mA Out Channels 7&8
Figure. 5.5.4. - 132. Example of the effects mA output Channel settings have.
Table. 5.5.4. - 108. mA output channel settings
Name
Range
Step
Default
Description
Enable mA Out
Channel
0:Disabled
1:Enabled
-
0:Disabled
Enables the mA Output channel. If channel is disabled
channel settings are hidden.
mA Out
Channel
Magnitude
selection
0:Currents
1:Voltages
2:Powers
3:Imp./Adm.
4:Other
-
0:Currents
De nes the category of measurement used for mA output
control.
mA Out
Channel
Magnitude
Dependent on
category
selection
-
Dependent
on category
selection
De nes the measurement used for mA output control.
Available measurements depends on parameter mA Out
Channel Magnitude selection.
Input value 1
-10
7
…10
7
0.001
0
First input point in the mA output control curve.
Scaled mA
output value 1
0.00000…
24.00000mA
0.0001mA 0mA
mA output value when measured value is equal or less than
Input value 1.