Sx channel
0:Ch0
1:Ch1
3:Ch2
4:Ch3
5:Ch4
6:Ch5
7:Ch6
8:Ch7
-
0:Ch0
Selection of measurement channel in the selected module.
Sx Deg
C/Dec F
0:Deg C
1:Deg F
-
0:Deg C
Selection of the measurement temperature scale in between of Celsius
and Fahrenheit.
Sx
Measurement -
-
-
Display of the measurement value in selected degrees.
Sx sensor
Ok
Invalid
-
-
Display of the measured sensor data validity. If the sensor reading has
any problems the sensor data is set to “Invalid” and the alarms are not
activated.
Sx Enable
alarm 1
0:Disable
1:Enable
-
0:Disable
Enable / Disable selection of the Alarm 1 for the measurement channel x
Sx Alarm1
>/<
0:>
1:<
-
0:>
Selection of the measurement higher or lower than setting value mode.
Sx Alarm1
-101.0…
2000.0deg 0.1deg 0.0deg
Alarm 1 setting value. Alarm shall be activated if the measurement is
over or under this setting depend of the selected mode.
Sx sensor
Ok
Invalid
-
-
Display of the measured sensor data validity. If the sensor reading has
any problems the sensor data is set to “Invalid” and the alarms are not
activated.
Sx Enable
alarm 2
0:Disable
1:Enable
-
0:Disable
Enable / Disable selection of the Alarm 2 for the measurement channel x
Sx Alarm2
>/<
0:>
1:<
-
0:>
Selection of the measurement higher or lower than setting value mode.
Sx Alarm2
-101.0…
2000.0deg 0.1deg 0.0deg
Alarm 2 setting value. Alarm shall be activated if the measurement is
over or under this setting depend of the selected mode.
When the RTD:s are set for measuring the values can be read to scada etc. and also the set alarms
can be used for direct output control from the RTD module or the alarms can be used in the logics as
well.
Events and registers
The RTD function generates events and registers from the status changes of start, trip and blocked. To
main event buffer is possible to select status “On” or “Off” messages. The RTD function offers four
independent instances which events are segregated for each instance operation.
In the function is available 12 last registers where the triggering event of the function (start, trip or
blocked) is recorded with time stamp and process data values.
Table. 5.4.11. - 88. Event codes of the RTD alarms
Event Number
Event channel
Event block name
Event Code
Description
4416
69
RTD1
0
S1 Alarm1 On
4417
69
RTD1
1
S1 Alarm1 Off
4418
69
RTD1
2
S1 Alarm2 On
4419
69
RTD1
3
S1 Alarm2 Off
4420
69
RTD1
4
S2 Alarm1 On
4421
69
RTD1
5
S2 Alarm1 Off
4422
69
RTD1
6
S2 Alarm2 On
4423
69
RTD1
7
S2 Alarm2 Off
AQ-T216
Instruction manual
Version: 2.00
161
© Arcteq Relays Ltd