4573
71
DIF1
29
LV I0d> Block Off
4574
71
DIF1
30
LV I0d> Trip On
4575
71
DIF1
31
LV I0d> Trip Off
Table below is presents the structure of DIF function register content. This information is available in 12
last recorded events.
Table. 5.4.10. - 86. Register content
Date & Time
Event
code
L1 Bias
current
L1 Diff
current
L1 Char
current
L2 Bias
current
L2 Diff
current
L2 Char
current
dd.mm.yyyy
hh:mm:ss.mss
4544-
4575 Descr.
Registered
L1 Bias
current
Registered
L1 Diff
current
Registered L1
max diff current
with bias
Registered
L2 Bias
current
Registered
L2 Diff
current
Registered L2
max diff current
with bias
L3 Bias
current
L3 Diff
current
L3 Char current
HV I0d> Bias
current
HV I0d>
Differential
current
HV I0d>
Characteristics current
Registered
L3 Bias
current
Registered
L3 Diff
current
Registered L3 max
diff current with bias
Registered HV side
REF Bias current
Registered HV
side REF Diff
current
Registered HV side REF
max diff current with bias
LV I0d> Bias current
LV I0d> Differential
current
LV I0d> Characteristics
current
SG in use
Ftype
Registered LV side REF
Bias current
Registered LV side REF
Diff current
Registered LV side REF max diff
current with bias
Used
setting
group
Detected fault type
(faulty phases)
5.4.11. Resistance temperature detectors (Modbus IO) (RTD) (49T)
Resistance Temperature Detectors (RTD) can be used to measure temperatures from the motor as well
as ambient temperature. Typically RTD is PT100 type or thermocouple. External Modbus based RTD
modules are supported up to three separate modules which each can hold up to eight measurement
elements. For the alarm function (RTD / 49T) can be set 12 individual element monitors which each
can be set to alarm two separate alarms from the selected input. Alarms and measurements can be
set in either degrees Centigrade or Fahrenheit.
The principal structure of RTD alarm function is shown in following gure.
To set the RTD measurement rst the measurement module needs to be set to scan the wanted RTD
elements. Currently Modbus based modules are supported. For the communication rst needs to be
set bitrate, databits, parity, stopbits and ModbusIO protocol. These are set at
Communication
→
Connections
.
After the communication is set the wanted channels are selected from the ModbusIO tab under
Communication
→
Protocols
. There are three separate modules available for selection.
Used measurement module is selected rst and the poll address. Module type needs to be set also as
well as the polled channels.
In case of thermocouple module the thermo element type needs to be set per each measurement
channel. After these settings the RTD:s are available for other functions.
AQ-T216
Instruction manual
Version: 2.00
159
© Arcteq Relays Ltd